Yaskawa iQpump Programming Manual User Manual

Page 55

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

55

Function: PI SFS Cancel (Setting: 34)

SFS means softstart, also referred to as accel/decel in this description.

By configuring a digital input as a PI SFS (softstart) Cancel input (H1-0x = 34), the operator will be able to use a contact closure to

remove the acceleration and deceleration times that are applied to changes in the PI setpoint by the b5-17 parameter. If the digital input

configured as PI SFS Cancel is closed, the PI setpoint Accel/Decel (Parameter b5-17) will be ignored. Immediate updating of any change

to the setpoint will apply.

Function: Input Level Sel (Setting: 35)

When using the PI Function built into the Drive, the chosen setpoint is compared with the measured feedback. The difference is called the

Error. The proportional and integral function are applied to this error. For some applications it may be appropriate to invert the input to

the PI block. This can be accomplished by setting one of the digital inputs up as an Input Level Sel (H1-0x=35). When an Input Level Sel

digital input is closed the Error will be inverted before it is passed to the PI block.

Figure 1.40

Figure 40 PI Error signal Inversion Block Diagram

Function: Option/Inv Sel 2 (Setting: 36)

The Option/Inv Selection function allows the user to switch the source of the Run and speed command between the Drive’s terminals and

optional communication card. When a digital input is programmed for the Option/Inv Selection 2 function (H1-0x = 36) that input will

function as follows:

Table 12 Programming Choices

To switch the command source between the option card and the terminals be sure to program the following parameters:

• Set b1-01 (Frequency Reference Selection) to 1 (Terminals).

• Set b1-02 (Run Command Selection) to 1 (Terminals).

• Set H1-0x (Input Terminal Function Selection) to 36.

Important: Switching the Reference and RUN sources can only be done while the iQpump drive is stopped.

Option/Inv Function Input Status

Run and Speed Command Source

CLOSED

From the Communications Option Card

OPEN

From the control circuit and analog input terminals

Set

Point

+

-

Z

-1

PI Block

Feed

back

H1=0x=35

OP

CLOSED

Open

Closed

Advertising