Yaskawa iQpump Programming Manual User Manual

Page 190

Advertising
background image

190

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

o1-07

0518H

Second Line User
Monitor Selection
2nd Monitor Sel

Sets the “U1” monitor always displayed on the 4th line of the digital
operator display. Effective only when o1-06 = 1.

1 to 94

2**

Programming

115

o1-08

0519H

Third Line User Monitor
Selection
3rd Monitor Sel

Sets the “U1” monitor always displayed on the 5th line of the digital
operator display. Effective only when o1-06 = 1.

1 to 94

91**

Programming

115

Key Selections

o2-01

0505H

Local/Remote Key
Function Selection
Local/Remote Key

Has no function when HOA operator is connected.
0: Disabled
1: Enabled

0 or 1

1

Programming

116

o2-02 0506H

OFF Key Function
During Auto Run
Oper OFF Key

Determines if the off key on the digital operator will stop the Drive
when Drive is operating from external terminals or serial
communications.
0: Disabled
1: Enabled

0 or 1

1

Programming

116

o2-03

0507H

User Parameter Default
Value
User Defaults

Allows storing of current parameter values as a User Initialization
Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as user initialization.
A1-03 now allows selecting <1110> for user initialization.
2: Clear All (Clears the currently saved user initialization. A1-03 no
longer allows selecting <1110>.

0 to 2

0

Programming

116

o2-04

0508H

Drive/kVA Selection
Inverter Model #

Sets the kVA of the Drive. Enter the number based on Drive Model #.
Use the ………… portion of the CIMR-P7…………-107 Model
Number.

0 to FF

kVA

Dependent

Programming

117

o2-05

0509H

Frequency Reference
Setting
Method Selection
Operator M.O.P.

Determines if the Data/Enter key must be used to input a frequency
reference from the digital operator.
0: Disabled - Data/Enter key must be pressed to enter a frequency
reference.
1: Enabled: -Data/Enter key is not required. The frequency reference is
adjusted by the up and down arrow keys on the digital operator without
having to press the data/enter key.

0 or 1

0

Programming

118

o2-06

050AH

Operation Selection
when Digital Operator is
Disconnected
Oper Detection

Determines if the Drive will stop when the digital operator is removed.
0: Disabled - The Drive will not stop when the digital operator is
removed.
1: Enabled - The Drive will fault (OPR) and coast to stop when the
operator is removed.

0 or 1

1

Programming

118

o2-07

050BH

Cumulative Operation
Time Setting
Elapsed Time Set

Sets the initial value of the elapsed operation timer.

0 to 65535

0 H

Programming

118

o2-08

050CH

Cumulative Operation
Time Selection
Elapsed Time Run

Sets how time is accumulated for the elapsed timer (o2-07).
0: Power-On Time (Time accumulates whenever Drive is powered).
1: Running Time (Time accumulates only when Drive is running)

0 or 1

1

Programming

118

o2-10

050EH

Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Se

t

Sets the initial value of the heatsink fan operation time.

0 to 65535

0 H

Programming

119

o2-12

0510H

Fault Trace/Fault History
Clear Function
FLT Trace Ini

t

Clears the fault memory contained in the U2 and U3 monitors.
0: Disabled (no effect).
1: Enabled - resets U2 and U3 monitors, and returns o2-12 to zero.

0 or 1

0

Programming

119

o2-14

0512H

kWh User Monitor (U1-
29) Initialization
kWh MonitorClear

Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change).
1: Clear all - Resets U1-29 to zero and returns o2-14 to zero.

0 or 1

0

Programming

119

COPY Function

o3-01

0515H

Copy Function Selection
Copy Function Sel

This parameter controls the copying of parameters to and from the
digital operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from the Drive to the
digital operator.
2: OP -> INV WRITE - All parameters are copied from the digital
operator into the Drive.
3: OP<-->INV VERIFY - Parameter settings in the Drive are compared
to those in the digital operator.
Note:

When using the copy function, the Drive model number and

software number (U1-14) must match or an error will occur.

0 to 3

0

Programming

120

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

Advertising