136

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Figure 1.103

Figure 108

Total setpoint compensation can be monitored with Total Setpoint Compensation (U1-93).

P2-09 Setpoint Compensation

Setting Range:

0.0 to 6000.0

Factory Default: 0.0

The iQpump drive can automatically increase the setpoint each time the maximum number of cycles programmed in Sleep Mode:

Cycling Protection (P2-06). The units for this parameter are determined by the System Units (P1-02).

Refer to Over-Cycling Mode: (P2-08 = 3: Auto Compensation) for further description.

P2-10 Maximum Setpoint Compensation

Setting Range:

0.0 to 6000.0

Factory Default: 0.0

The iQpump drive can set the maximum allowable setpoint compensation during an over-cycling condition by the value programmed in

Maximum Setpoint Compensation (P2-10). The units for this parameter are determined by the System Units (P1-02).

Refer to Over-Cycling Mode: (P2-08 = 3: Auto Compensation) for further description.

P2-11 No-Flow Activation Level

Setting Range:

0 to 24000 RPM

Factory Default: 0 RPM

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). The no-

flow detection is active when the motor is operating below this No-Flow Activation Level (P2-11) and below the No-Flow Detection

Bandwidth (P2-12).

Setting P2-11 to a value of 0 will disable this function. This function is only active during operation in the Auto Mode and when the drive

is operating above the Minimum Pump Frequency (P1-06) and below the level programmed in P2-11.

Note: Program Start Level (P1-04) to a value greater than 0.

The No-Flow Activation Level (P2-11) works in conjunction with the No-Flow Detection Bandwidth (P2-12).

No-Flow Detection Basic Operation

The iQpump drive can be configured for a no-flow detection condition. The no-flow detection function of the iQpump drive is an

advanced feature for all pumping applications. The typical applications for this function are submersible and booster station pumps.

TIME

System Running Auto Mode

Auto Mode Run

Sleep Mode

AUTO MODE

RUN

AUTO MODE

RUN

AUTO MODE

RUN

SLEEP

SLEEP

Cycle Count

Register

Cycle

Count = 1

Cycle

Count = 2

P2-06 Max. Cycle = 3
P2-09 Set-Point Comp = 1.0
P2-10 Max. SP Comp. = 10.0

Cycle

Count = 0

Cycle

Count = 1

Maximum cycle count exceeded,

Increase Set-Point with Value of P2-09.

Total Compensation not to exceed P2-10

SLEEP

Cycle

Count = 3

Cycle

Count = 2

INCR. SET-POINT by P2-09