Figure 1.63

Figure 63 Output Frequency with Reduced Bias Setting

As a further example, for an inverse-acting speed command, set the bias = 100% and the gain = 0%. The minimum analog input level (0

Vdc or 4 mA) will produce a 100% speed command and the maximum analog input level (10 Vdc or 20 mA) will produce a 0% speed

command.

Figure 1.64

Figure 64 Output Frequency with Inverted Gain and Bias Settings

H3-08 Terminal A2 Signal Level

The H3-08 parameter (Terminal A2 Signal Level) allows the programmer to specify the signal that will be applied to the A2 analog input.

The A2 analog input can accept either a 0–10 Vdc or 4-20 mA signal as a reference. The iQpump drive also has a DIP switch (S1) on the

removable terminal board that must be set for the proper reference signal into the A2 analog input. The S1-2 dipswitch setting determines

the internal resistance of the A2 input while parameter H3-08 determines how the iQpump drive interprets the measured signal.

Setting

Description

0

0 - 10 Vdc

2

4 - 20 mA (factory default)

3

0 - 20 mA

0V

4mA

10V

20mA

Gain = 100%

Bias = -25%

O

ut

put

F

req

ue

ncy

Analog Input Level

2.5V
8mA

Analog Input Signal

20mA

4mA

0V

10V

Gain = 100%

Bias = 0%

Out

put

F

req

uen

cy

Analog Input Level

Analog Input Signal

Bias

Gain