Yaskawa iQpump Programming Manual User Manual

Page 151

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

151

If P3-01 = 2: Output Frequency + Feedback Level

The de-staging (turning OFF) of the auxiliary pump occurs when the output frequency drops below the level programmed in the Pump 3

Frequency Shutdown Level (P3-10) or Pump 2 Frequency Shutdown Level (P3-09) and the difference (delta) between the system’s

feedback level minus setpoint has exceeded the level programmed in the Shutdown Pump Delta Level (P3-05) for the time programmed

in the Shutdown Pump Delay Time (P3-06).

The auxiliary pumps will be added by the control of the multi-function digital output contact closure (H2-xx = 40 and 41).

P3-06 Shutdown Pump Delay Time

Setting Range:

0 to 3600 sec

Factory Default: 5 sec

The de-staging (turning OFF) of the auxiliary pumps will occur after the time delay programmed in the Shutdown Pump Delay Time (P3-

06) has elapsed. The time delay will occur prior to de-staging of the auxiliary pumps.

The Shutdown Pump Delay Time (P3-06) works in conjunction with iQpump drive Multi/Maximum Level (P3-02) and Add Pump Delta

Level (P3-03).

Refer to Lead-Lag Control (P3-01) for further description of de-staging of the pump system.

P3-07 Multi Pump Setpoint Increase

Setting Range:

0.0 to 6000.0

Factory Default: 0.0

The iQpump drive can be configured for multiplex pumping operation. The multiplex pumping operation can have the system setpoint

increased each time a pump is staged (turned ON) by programming the amount to be increased into the Multi Pump Setpoint Increase

(P3-07). The system’s setpoint will be lowered by this amount when each pump is de-staged (turned OFF). Refer to

Figure 120

below.

The units for this parameter are determined by the System Units (P1-02).

Example: Constant Pressure System

System Setpoint: 80PSI

Pressure Transducer: 150PSI

Multi Pump Setpoint Increase: 4PSI

Pump 1 (Running) Setpoint = 80PSI

Pump 1 + Pump 2 (Running) Setpoint = 84PSI (80PSI + 4PSI)

Pump 1 + Pump 2 + Pump 3 (Running) Setpoint = 88PSI (80PSI + 4PSI + 4PSI)

CAUTION

Do not program this level too close to the system’s setpoint.
If the level is too close to the setpoint, excessive cycling of the pump system may occur.