YASKAWA TM.iQp.02 iQpump Drive Programming Manual

63

H2 Digital Outputs

Terminal Function Selections

Setting Range:

0 to 42

Factory Defaults: H2-01 = “40: Pump 2 Control”

H2-02 = “41: Pump 3 Control”

The iQpump drive has two multi-function outputs. By programming parameters H2-01 and H2-02, the user can assign specific functions

to each output. Below is a table with a complete list of all of the digital output functions. Because the iQpump drive is a dedicated pump

controller, the digital outputs described in this section only relate to the pump specific functions. Following the table is a more detailed

description of each of the pump related functions.

Table 16 Digital Output Functions

Function: During Run 1 (Setting: 0)

A “During Run 1”output will close whenever the Run command is provided and the iQpump drive is outputting voltage. This will include

deceleration and DC Injection.

Function: Zero Speed (Setting: 1)

The “Zero Speed” output will close whenever the output frequency falls below the Minimum Frequency (E1-09).

Function: Fref/Fout Agree 1 (Setting: 2)

The “Fref/Fout Agree 1” output will close whenever the actual output frequency is within the Speed Agree Width (L4-02) of the current

Speed Command regardless of the direction.

Parameter No.

Parameter Name

H2-01

Terminal M1-M2 Function Selection

H2-02

Terminal M3-M4 Function Selection

Parameter setting

Function

Parameter setting

Function

0

During Run1

11

Reset Cmd Active

1

Zero Speed

12

Timer Output

2

FREF/FOUT Agree 1

17

Torque Detect 1 N.C.

3

FREF/Set Agree 1

1A

Reverse Direction

4

Frequency Detect 1

1E

Restart Enabled

5

Frequency Detect 2

1F

Overload (OL1)

6

Drive Ready

20

OH Pre-alarm

7

DC Bus Undervoltage

28

Drive Enable

8

Baseblock 1

39

Drive Waiting

9

Option Reference

3A

Frequency Reduced, OH

A

Remote Operation

3B

Run from Serial Com

B

Torque Detect 1 N.O.

3D

Cooling Fan Err

C

Loss of Reference

40

Pump 2 Control

E

Fault

41

Pump 3 Control

F

Terminal Not Used

42

Pump Fault

10

Minor Fault