YASKAWA TM.iQp.02 iQpump Drive Programming Manual

107

L6 Torque Detection

L6-01 Torque Detection Selection 1

L6-02 Torque Detection Level 1

Setting Range:

0 to 300% of the iQpump drive rated output current

Factory Default: 15% of the iQpump drive rated output current

L6-03 Torque Detection Time 1

Setting Range:

0.0 to 10.0 sec

Factory Default: 10.0 sec

The iQpump drive can be programmed to indicate when either an overtorque or an undertorque conditions exist. A digital output must be

programmed for “Torque Detection,” (H2-01/H2-02 = “B: Trq Det 1 N.O.” or “17: Trq Det 1 N.C.). A warning of an overtorque

condition can indicate a jam and an undertorque condition can indicate a broken belt, no water in a pump, or other loss of load.

To configure Torque Detection requires the following decisions:

1. Do you wish to check for an overtorque condition or an undertorque condition?
2. Do you wish to check for the torque condition whenever the drive is running or only at speed agree? Nuisance detection during

acceleration, when variable torques are normally required, can be avoided.

3. Do you want the drive to fault if the torque condition is detected or only alarm and continue operation?

The following table can help choose the proper setting for Torque Detection Selection 1 to get the wanted results.

Table 28 L6-01 Setting Choices

After selecting the proper detection scheme the Torque Detection Level (L6-02) must be specified. If the current level read by the output

current transformers rises above (overtorque) or drops below (undertorque) this level, and remains there for at least the Torque Detection

Time (L6-03), then the Torque Detection Function will change the state of any digital output configured for Torque Detection (H2-01/

H2-02 = “B: Trq Det 1 N.O.,” or “17: Trq Det 1 N.C.”).

Setting

Description

0

Disabled (

factory default)

1

OL@SpdAgree - Alm

2

OL At Run -Alm

3

OL@SpdAgree - Flt

4

OL At Run - Flt

5

UL@SpdAgree - Alm

6

UL at Run - Alm

7

UL@SpdAgree - Flt

8

UL At Run - Flt

L6-01

Setting

Overtorque

Undertorque

Fault

Alarm

Always Detected

Only Detected @

Spd Agree

0

Torque Detection Disabled

1

X

X

X

2

X

X

X

3

X

X

X

4

X

X

X

5*

X

X

X

6

X

X

X

7

X

X

8

X

X

*Suggested settings for Loss of Load indication