Sleep mode sleep permitted – Yaskawa iQpump Programming Manual User Manual

Page 142

Advertising
background image

142

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Figure 1.108

Figure 113

The sleep function can be active during the following conditions:

• When P2-20 is set to 0 (disabled), the output frequency must be greater than the Sleep Level (P2-02).

• When P2-20 is greater than P2-02, the output frequency must be greater than Alternative Sleep Activation Level (P2-20). See

Figure 111

.

• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level

(P2-20). See Figure 112.

• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level

(P2-20) and Sleep Level (P2-02). See Figure 113.

A value of 0 programmed in P2-20 will disable this function.

The Alternative Sleep Activation Level (P2-20) works in conjunction with the Start Level (P1-04) and the Sleep Level Type (P2-01).

Note: It is recommended that P2-20 be programmed 1 or 2 Hz above the P1-06 value. The sleep level using P2-20 enables the

sleep mode; however, the drive still enters sleep based on P2-20. With the normal default sleep level programmed in

P2-02, the sleep cycle will not activate until the output frequency is above P2-02.

P1-06

SLEEP MODE

SLEEP PERMITTED

P2-02

P2-20

P2-03

Advertising