YASKAWA TM.iQp.02 iQpump Drive Programming Manual

81

H5 Serial Communications Setup

This section explains the individual functions used in special applications involving Modbus Communications.

Using Modbus Communication

Serial communication can be performed with Programmable Logic Controllers (PLC’s) or similar devices using the Modbus protocol.

Modbus Communication Configuration

Modbus communication is configured using 1 master (PLC) and a maximum of 31 slaves. Serial communication between master and

slave is normally initiated by the master and responded to by the slaves.

The master performs serial communication with one slave at a time. Consequently, the slave address of each slave must be individually

set, so that the master can perform serial communication using that address. Slaves receiving commands from the master perform the

specified functions, and send a response back to the master.

Figure 1.76

Figure 76 Example of Connections between Master and Drive

Communication Specifications

The Modbus communication specifications are shown below:

Table 19 Modbus Communication Specifications

Communication Connection Terminal

Modbus communication uses the following terminals: S+, S-, R+, and R-. The terminating resistance must be turned ON only if the

iQpump drive is at the very end of the Serial Communication chain. Set the terminating resistance by turning ON pin 1 of switch S1 On

the Drives terminal board. Switch S1 is located directly above the left most relay module.

Item

Specifications

Interface

RS-422, RS-485

Communications Cycle

Asynchronous (Start-stop synchronization)

Communications Parameters

Baud rate:

Select from 1200, 2400, 4800, 9600, and 19200 bps.

Data length:

8 bits fixed

Parity:

Select from even, odd, or none.

Stop bits:

1 bit selected

Communications Protocol

Modbus

Number of Connectable Units

31 units max.

Master

iQpump

iQpump

iQpump

Slaves