Iqpump basic programming parameters, A1 initialization, A1-01 access level selection – Yaskawa iQpump Programming Manual User Manual

Page 8: A1-03 initialize parameters

Advertising
background image

8

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

iQpump Basic Programming Parameters

The initialization group contains parameters associated with initial set-up of the Drive. Parameters involving the display language, access

levels, initialization and password are located in this group.

A1 Initialization

A1-01 Access Level Selection

If the iQpump drive is programmed for Operation Only (A1-01 = “0: Operation Only”), then only the OPERATION and the

PROGRAMMING menus are accessible. Within the PROGRAMMING menu only parameters A1-01 and A1-04 are adjustable.

If A1-01 is configured for Advanced Access (A1-01 = “2: Advanced Level”), then all menus and all parameters are shown. If the Access

Level Selection is set to Advanced, all parameters should be adjustable unless:

1. The iQpump drive parameters are password protected (A1-04) which will prevent access to A1-00 through A1-03 and all A2

parameters.

2. A digital input has been configured as a Program Lockout (H1-0X = 1B) is active.
3. During serial communication writing, if a parameter change is also attempted via the digital operator, a “BUSY - WRITE

PROTECTED” message will display. Parameter change will not be possible from the digital operator until an Enter command is

received via the serial communication to finish the serial writing process.

A1-03 Initialize Parameters

The iQpump drive can be set back to one of three default states via the A1-03 parameter.

1. User Initialization – 1110: The modified iQpump drive parameters are returned to the values selected as user settings. User settings are

stored when parameter o2-03 = “1: Set Defaults”.

2. 2-Wire Initialization – 2220: The iQpump drive parameters are returned to factory default values with digital inputs S1and S2

configured as Forward Run and Reverse Run, respectively.

3. 3-Wire Initialization – 3330: The iQpump drive parameters are returned to factory default values with digital inputs S1, S2, and S5

configured as Run, Stop, and Forward/Reverse respectively.

After an initialization is performed, parameter A1-03 will automatically be set back to 0.

Figure 1.1

Figure 1 2 & 3-Wire Control Wiring Examples

Setting

Description

0

Operation Only

2

Advanced Level (factory default)

Setting

Description

0

No Initialize (factory default)

1110

User Initialize

2220

2-Wire Initialize

3330

3-Wire Initialize

SN

S2

S1

S1

S2

SN

FWD Run/Stop

REV Run/Stop

2-wire control

2-wire control

Stop switch
(NC contact)

Operation switch
(NO contact)

Run command

(run on momentary close)
Stop command
(stop on momentary open)

Sequence input common

3-wire control