L5 fault restart, L5-01 number of auto restart attempts, L5-02 auto restart operation selection – Yaskawa iQpump Programming Manual User Manual

Page 105: L5-03 maximum restart time after fault

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

105

L5 Fault Restart

L5-01 Number of Auto Restart Attempts

Setting Range:

0 to 10

Factory Default: 0

L5-02 Auto Restart Operation Selection

L5-03 Maximum Restart Time After Fault

Setting Range:

10.0 to 3600.0 sec

<0032>

Factory Default: 180.0 sec

All major faults will cause the iQpump drive to stop. For some faults it is possible to configure the iQpump drive to attempt a restart

automatically. After the fault occurs, the iQpump drive baseblocks for the Maximum Restart Time After Fault programmed in L5-03.

After the baseblock is removed the iQpump drive checks if a fault condition still exists. If no fault condition exists the iQpump drive will

attempt to restart the motor. If the restart is successful, the iQpump drive performs a Speed Search (Regardless of the status of b3-01

“Speed Search Selection”) from the set speed command and the Auto Restart Attempts count is increased by one. Even if the restart fails

the restart count is increased by one as long as the iQpump drive attempted to rotate the motor. The restart count will not be incremented

if the restart is not attempted due to a continuing fault condition, (i.e. an OV fault). The iQpump drive waits the Maximum Restart Time

After Fault (L5-03) before attempting another restart. This parameter is not applicable to Loss of Prime Fault.

Figure 1.90

Figure 95 Automatic Restart Timing Diagram

The auto restart count is reset back to 0 if any of the following occur:

• No further faults for ten minutes after the last retry.

• The Drives power is turned off (the iQpump drive must be without power long enough to let control power dissipate).

• The SHIFT/RESET key is pushed after the last reset attempt.

The setting of parameter L5-02 determines whether the fault output (MA-MB) will be closed during an auto restart attempt. The setting

of L5-02 can be important when interfacing the iQpump drive with other equipment.

The following faults will allow the Auto Restart function to initiate:

• OC (Overcurrent)

• LF (Output Open Phase)

• PF (Input Phase Loss)

• PUF (DC Bus Fuse)

Setting

Description

0

No Flt Relay (

factory default)

1

Flt Relay Active

t

t

t

t

Run

Fault

Attempts

Count

L2-03

OV

trying each

L5-03 seconds successful

1

OC

L2-03

2

Voltage
remains high
for a long time,
then reset (1)

L2-03

3

OC

OC condition
gone, resets (3)
and runs.

successful

try but failed

Drive trips on OC,
resets (2) and tries
again but motor still
shorted, trips again.

TIME