YASKAWA TM.iQp.02 iQpump Drive Programming Manual

17

Figure 1.12

Figure 12 Coast to Stop with Timer

b1-08 Run Command Selection During Programming

As a safety precaution, the iQpump drive will not normally respond to a Run input when the digital operator is being used to adjust

parameters. If it is necessary that external Run commands be recognized even while the Drive is being programmed, set b1-08 = “1:

Enabled.”

b1-11 Drive Delay Time Setting

Setting Range:

0 to 600 sec

Factory Default: 0 sec

If a time is set into parameter b1-11, the iQpump drive will delay executing any run command until the b1-11 time has expired. During

iQpump drive delay time execution, the digital operator will display:

Both the ALARM and Run indicators will blink while the iQpump drive waits to execute the Run command.

Setting

Description

0

Disabled (factory default)

1

Enabled

Run Command

Output Frequency

Drive Output

Voltage

Interrupted

OFF

ON

Timer Value T

(C1-02)

100 %

0 %

Operat

io

n W

ai

t T

im

e (T

)

Deceleration

Time (C1-02)

Minimum

Baseblock

Time (L2-03)

Minimum

Output

Frequency

100% (Maximum

Output

Frequency)

Output Frequency at Stop Command Input

Ignored

Run Command

Timer Value T

(OPEN)

(CLOSED)

DDLY

Waiting to RUN