o2-04 Drive / kVA Selection

Setting Range:

0 to FF

Factory Default: Model Dependent

Parameter o2-04 matches the control board to the iQpump drive hardware. Proper setting of o2-04 is important so that the control board

can provide proper protection for the iQpump drive hardware. This parameter is configured at the factory and does not normally require

adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.

Table 29 kVA Settings by iQpump Drive Model Number

The factory defaults of the following parameters may be changed when the setting of o2-04 is changed:

• b8-04 (Energy Saving Coefficient Value)

• C6-02 (Carrier Frequency Selection)

• E2-01 (Motor Rated Current)

• E2-03 (Motor No-Load Current)

• E2-05 (Motor Line-to-Line Resistance)

• L2-02 (MPL Ride-Thru Time)

• L2-03 (MPL Minimum Base Block Time)

• L2-04 (MPL Voltage Recovery Ramp Time)

• L8-02 (Overheat Pre-Alarm Level)

• L8-06 (Input Phase Loss Detection Level)

208-230/240 Vac

480 Vac

Model Number

Proper

o2-04 Setting

Model Number

Proper

o2-04 Setting

20P4

0

40P4

20

20P7

1

40P7

21

21P5

2

41P5

22

22P2

3

42P2

23

23P7

4

43P7

24

27P5

6

45P5

26

2011

7

47P5

27

2015

8

49P0

3C

2018

9

4011

28

2022

A

4015

29

2030

B

4018

2A

2037

C

4022

2B

2045

D

4024

3D

2055

E

4030

2C

2075

F

4037

2D

2090

10

4045

2E

2110

11

4055

2F

4075

30

4090

31

4110

32

4160

34

4185

35

4220

36

4300

37