Carrier frequency limits, C6-05 carrier frequency proportional gain – Yaskawa iQpump Programming Manual User Manual

Page 35

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

35

Carrier Frequency Limits

Setting Range:

0.4 to 10.0 kHz

Factory Default: Model Dependent

C6-05 Carrier Frequency Proportional Gain

Setting Range:

0 to 99

Factory Default: 0

It is possible to configure the iQpump drive such that the carrier frequency will automatically increase as the output frequency is raised

(synchronous carrier). A synchronous carrier can be used by setting parameter C6-02=F: Program. The profile of the carrier frequency is

show below and can be configured to the users specification by setting the carrier frequency upper and lower limits (C6-03 and C6-04

respectively) and a carrier frequency proportional gain (C6-05).

Figure 1.27

Figure 27 Synchronous Carrier Frequency Characteristics

The frequencies that correspond to the breakpoints a and b will be determined by the value of K given in the table below and the

following formulas:

Important: If C6-05 > 6 and C6-04 > C6-03 the iQpump drive will fault and display and OPE11 error.

2090

1 (2.0)

1 (2.0)

1 (2.0)

0

125

4110

2 (5.0)

2 (5.0)

2 (5.0)

0

200

2110

1 (2.0)

1 (2.0)

1 (2.0)

0

150

4160

2 (5.0)

2 (5.0)

2 (5.0)

0

250

4185

1 (2.0)

1 (2.0)

1 (2.0)

0

300/350

4220

1 (2.0)

1 (2.0)

1 (2.0)

0

450

4300

1 (2.0)

1 (2.0)

1 (2.0)

0

500+

Parameter No.

Parameter Name

C6-03

Carrier Frequency Upper Limit

C6-04

Carrier Frequency Lower Limit

Conditions

K Value

C6-03 > 10.0 kHz

3

10.0 kHz > C6-03 > 5.0 kHz

2

C6-03 < 5.0 kHz

1

208 V – 240 V Drives 1

480 V Drives 1

Model

CIMR-P7

C6-02

Carrier

Frequency

(kHz)

C6-03

Carrier

Frequency

Max. (kHz)

C6-04

Carrier

Frequency

Min. (kHz)

C6-05

Carrier

Frequency

Gain

Nominal

HP

Model

CIMR-P7

C6-02

Carrier

Frequency

(kHz)

C6-03

Carrier

Frequency

Max. (kHz)

C6-04

Carrier

Frequency

Min. (kHz)

C6-05

Carrier

Frequency

Gain

Nominal

HP

C6-03

C6-04

C6-05 x K

f

out

f

c

a

b

a

b

C6-04

a

C6-04

C6-05

K

×

--------------------------

=

b

C6-03

C6-05

K

×

--------------------------

=