P4-02 pre-charge frequency – Yaskawa iQpump Programming Manual User Manual

Page 163

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

163

Figure 1.126

Figure 131

P4-02 Pre-Charge Frequency

Setting Range:

0.0 to 120.0 Hz

Factory Default: 0.0 Hz

The iQpump drive can be configured for a pre-charge function. The frequency reference used by the pre-charge function is programmed

in the Pre-Charge Frequency (P4-02).

Refer to Pre-Charge Level (P4-01) for further description.

The Pre-Charge Frequency (P4-02) works in conjunction with the Pre-Change Level (P4-01).

Run
Command

Hand Frequency

Pre-Charge
Frequency P4-02

Thrust Bearing
Frequency P4-05

Pre-Charge
Level P4-01

TIME

Thrust Bearing Mode and Pre-Charge Function with Alternating Auto and Hand Mode.

PI Feedback

Hand
Mode

Pre-Charge
Frequency P4-02

Thrust Bearing
Frequency P4-05

Standard
Accel Time
C1-01

Thrust
Bearing Accel
Time P4-04

Pre-Charge
Complete

Standard
Decel Time
C1-02

Thrust Bearing
Decel Time P4-06

Stop due to Run
Command Removed

Output Frequency

Frequency Reference
Limited because
Hand Frequency < P4-05

@ Hand
Frequency