TM.iQp.02 iQpump Drive Programming Manual

P1-11



<0032>

0106H

Maximum SetPoint
Difference
Max Setpoint Diff

When the Drive is running and the difference between the setpoint and
the feedback exceeds the level in P1-11 for the time specified in P1-12,
the Drive will trip on a “Not Maintaining Setpoint (NMS)”. The Drive
will coast to a stop when a fault occurs. A value of 0 disables this
function. This function is only active during running while operating in
auto mode.

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Pump Quick

Setup

126

P1-12



<0032>

0107H

Not Maintaining Setpoint
and Loss of Prime Time
Setpoint-LOP Tim

Delay time before a Not Maintaining Setpoint or Loss of Prime Time
fault occurs. Pump protection criteria specified in P1-11 or P1-14 must
be met for the Drive to fault. The Drive will coast to a stop when a fault
occurs. A value of 0 disables both Loss of Prime and Not Maintaining
Setpoint faults.

0 to 3600

60 sec

Pump Quick

Setup

127

P1-13



0108H

Hysteresis Level
Hysteresis Level

Hysteresis Level used for low and high feedback alarm detection. See
function P1-07 and P1-09.

0.0 to
100.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Programming

127

P1-14



0109H

Prime Loss Level
Prime Loss Level

Used to detect loss of prime in the pump. If output current drops below
this level for the time specified in P1-12 and the output frequency is at
fmax, a “Loss Of Prime” fault occurs. The Drive will coast to a stop
when a fault occurs.

0.0 to

1000.0

0.0 A

Pump Quick

Setup

127

P1-15



010AH

Low Water Input
Low Water Input

Sets the type of control operation
0: Closed at Low Water, (Closed indicates low water condition)
1: Open at Low Water, (Open indicates low water condition)
To use the low water function one of the digital inputs (H1-XX=85)
needs to be programmed. The low water input can be used for a low
water condition or in combination with the pre-charge function to
indicate the reservoir is filled. The low water input fault is only active
during running while operating in auto mode.

0 or 1

0

Programming

128

Pump Protection

P2-01

060AH

Sleep Level Type
Sleep Lvl Type

Sets the sleep type.
0: Output Frequency
1: Output Current
2: Feedback
Note:

Feedback depends on PID direction operation.

Displays a “Sleep” Alarm when active.

0 to 2

0

Pump Quick

Setup

129

P2-02



060BH

Sleep Level
Sleep Level

Sleep activates when selected level (P2-01) reaches programmed sleep
level for time specified in P2-03. The level type is determined by P2-
01. A value of 0 disables this function. This function is only active
during running while operating in auto mode.
Display Units for Sleep Level P2-02 when P2-01 is programmed for
the following:
P2-01=0: >Display based on “Hz”
P2-01=1: >Display based on “A”
P2-01=2: >Display based on P1-02 Selection
Note:

When P2-01 is set for a value of 2, display units will be

dependent on P1-02 setting.

0.0 to

6000.0

0.0

Pump Quick

Setup

133

P2-03



060CH

Sleep Delay Time
Sleep Delay Time

Delay time before Drive enters sleep mode when criteria is met as
defined by parameter P2-02.

0 to 3600

10 sec

Pump Quick

Setup

133

P2-04



060DH

Delta Sleep Feedback
Drop Level
D Fb Drop Level

When the Drive enters sleep mode, the software monitors the feedback
to detect a flow-no flow condition. If the PID Error (setpoint minus
feedback) exceeds the programmed level P2-04 within the
programmed time (P2-05) and the output frequency is greater than the
minimum frequency (P1-06), the sleep operation deactivates and the
Drive returns to normal operation. A value of 0 disables this function.

0.0 to

6000.0

(system

units P1-

02)

0.0

(system

units P1-

02)

Programming

133

P2-05



060EH

Feedback detection drop
time.
FB Drop DetTime

Defines the time window in which the software monitors the feedback
to detect a flow-no flow condition. Works in conjunction with
parameter P2-04.

0 to 3600

10 sec

Programming

134

P2-06



060FH

Sleep Mode: Cycling
Protection
Cycle Protection

Maximum number of cycles allowed within the time specified in P2-07
before the Drive initiates a “Pump Cycle Fault (PCF)”. One Cycle is
defined when the Drive transfers from normal operation in auto mode
to sleep mode. A value of 0 disables this function.

0 to 10

0

Programming

134

P2-07



0610H

Sleep Mode: Maximum
Cycling Protection Time
Max. Cycle Time

Maximum time allowed between cycles. When no cycling occurs
within the programmed time, the Drive will reset the internal cycle
register. Works in conjunction with P2-06.

0 to 3600

300 sec Programming

135