Yaskawa iQpump Programming Manual User Manual

Page 139

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

139

P2-12 No-Flow Detection Bandwidth

Setting Range: 0 to 1000 RPM

Factory Default: 15 RPM

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). The no-

flow activation can have a programmed bandwidth before the no-flow condition is activated by programming the No-Flow Detection

Bandwidth (P2-12).

The No-Flow Detection Bandwidth (P2-12) sets the motor RPM fluctuation bandwidth. The no-flow detection activates when the motor

RPM is below the No-Flow Activation Level (P2-11) and remains within the programmed No-Flow Detection Bandwidth (P2-12) for a

time specified by the No-Flow Detection Time (P2-13).

The No-Flow Detection Bandwidth (P2-12) works in conjunction with the No-Flow Activation Level (P2-11).

Refer to the No-Flow Activation Level (P2-11) for further description.

P2-13 No-Flow Detection Time

Setting Range:

0.0 to 1000.0 sec

Factory Default: 5.0 sec

The iQpump drive can be configured to activate a no-flow condition by programming the No-Flow Activation Level (P2-11) and No-

Flow Detection Bandwidth (P2-12). The no-flow detection activates when the motor RPM remains within the programmed bandwidth

(P2-12) for a time programmed in the No-Flow Detection Time (P2-13).

The No-Flow Detection Time (P2-13) works in conjunction with the No-Flow Detection Bandwidth (P2-12) and the No-Flow Feedback

Level (P2-15).

Refer to the No-Flow Activation Level (P2-11) for further description.

P2-14 No-Flow Stabilization Time

Setting Range:

0.0 to 1000.0 sec

Factory Default: 5.0 sec

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). When the

no-flow detection is activated, the system setpoint will be lowered by the value programmed in the No-Flow Setpoint Compensation (P2-

16) for a specific time as programmed by the No-Flow Stabilization Time (P2-14). After the time programmed in P2-14 has elapsed, the

system setpoint will return to the original setting.

The No-Flow Stabilization Time (P2-14) works in conjunction with the No-Flow Setpoint Compensation (P2-16).

Refer to the No-Flow Activation Level (P2-11) for further description.

P2-15 No-Flow Delta Feedback Level

Setting Range:

0.0 to 6000.0

Factory Default: 1.0

The iQpump drive can be configured to activate a no-flow detection by programming the No-Flow Activation Level (P2-11). When the

no-flow detection is activated, the feedback level is monitored and compared to the system setpoint. If the difference between the system

setpoint and the feedback level exceeds the No-Flow Delta Feedback Level (P2-15) for a time specified by the No-Flow Feedback Delay

Time (P2-17), the drive will enter a “sleep” mode.

The No-Flow Delta Feedback Level (P2-15) works in conjunction with the No-Flow Feedback Delay Time (P2-17). The units for this

parameter are determined by the System Units (P1-02).

Refer to the No-Flow Activation Level (P2-11) for further description.

Note: The feedback detection direction can be selected by programming No-Flow Feedback Detection Direction (P2-19).