YASKAWA TM.iQp.02 iQpump Drive Programming Manual

145

Figure 1.110

Figure 115

The pump system can be allowed to stabilize by programming a time into the Multiplex Stabilization Time (P3-11). The Multiplex

Stabilization Time (P3-11) becomes active after an auxiliary pump is staged or de-staged.

Note: The pump protection function is disabled during auxiliary pump staging and de-staging.

The No-Flow and Sleep functions are only active when the lead pump controlled by the drive is the only pump operating the pump

system.

P3-01 = 1: Feedback Level

The “feedback level” control method monitors the drive’s output frequency and the system’s feedback level to determine if the auxiliary

pumps need to be staged (turned ON) to maintain the programmed system’s setpoint. The output frequency and the system’s feedback

also determine when the auxiliary pumps are to be de-staged (turned OFF). Refer to

Figure 116

and

Figure 117

for the staging and de-

staging of the auxiliary pumps using the “feedback level” control method.

Auxiliary Pump Staging (ON)

The staging of auxiliary pump 2 occurs when the difference between the system setpoint minus the feedback level exceeds the value

programmed in the Add Pump Delta Level (P3-03) for the time programmed in Add Pump Delay Time (P3-04).

The staging of auxiliary pump 3 occurs when the auxiliary pump 2 is staged and when the difference between the system setpoint minus

the feedback level exceeds the value programmed in the Add Pump Delta Level (P3-03) for the time programmed in Add Pump Delay

Time (P3-04). Refer to

Figure 116

for the staging of the auxiliary pumps using the “feedback level” control method.