Yaskawa iQpump Programming Manual User Manual

Page 44

Advertising
background image

44

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Table 7 V/f Pattern Default Settings for Drive Capacity 50 to 150 HP for 240 V Class

Parameter

No.

Name

Unit

Factory Setting

E1-03

V/f Pattern Selection

0

1

2

3

4

5

6

7

8

9

A

B

C

D

F

E1-04

Max. Output Frequency

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

90.0 120.0 60.0

E1-05

Max. Output Voltage

V

240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0 240.0

E1-06

Max. Voltage Frequency

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

60.0

60.0

60.0

E1-07

Mid. Output Frequency A

V

2.5

3.0

3.0

3.0

25.0

25.0 30.0

30.0

2.5

2.5

3.0

3.0

3.0

3.0

3.0

E1-08

Mid. Output Voltage A

V

13.8

13.8

13.8

13.8

40.2

57.5

40.2

57.5

17.2

23.0

17.2

23.0

13.8

13.8

13.8

E1-09

Min. Output Frequency

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

1.3

1.3

1.5

1.5

1.5

1.5

1.5

E1-10

Mid. Output Voltage

V

6.9

6.9

6.9

6.9

5.7

6.9

5.7

6.9

8.0

10.3

8.0

12.6

6.9

6.9

6.9

E1-11

Mid Output Frequency B

Hz

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

E1-12

Mid Output Voltage B

V

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

E1-13

Base Voltage

V

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

For 480 V class units, the value is twice that of 240 V class units.