P2-05 feedback detection drop time, P2-06 sleep mode: cycling protection – Yaskawa iQpump Programming Manual User Manual

Page 134

Advertising
background image

134

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Figure 1.102

Figure 107 No-Flow Detection During Deceleration

P2-05 Feedback Detection Drop Time

Setting Range:

0 to 3600 sec

Factory Default: 10 sec

The iQpump drive can be configured to detect a no-flow condition. The drive can be programmed to monitor the feedback signal during

a flow, no-flow condition for a programmed Feedback Detection Drop Time (P2-05).

The Feedback Detection Drop Time (P2-05) works in conjunction with the Delta Sleep Feedback Drop Level (P2-04).

P2-06 Sleep Mode: Cycling Protection

Setting Range:

0 to 10

Factory Default: 0

TIME

Output Frequency

Sleep Delay Time

P2-03

Feedback

Auto Mode Run

Sleep Active

Wait for Start

Sleep Level

P2-02

STOP, 0Hz

0%

OFF Mode

Start Level

P1-04

FB Drop

Check

AUTO MODE RUN

Ramp

Down

Start System, Incoming Run Command

Start System

Min. Frequency

P1-06

AUTO MODE RUN

Start Level Delay

P1-05

START DELAY

System

Set-Point

P2-04 Delta FB Drop Level

P2-05 Feedback Drop Detection Time

Sleep Detected

Feedback Drop

Detected