Function: Thermostat Fault (Setting:87)

<0032>

A digital input can be configured to indicate a Thermostat Fault from an external contact (H1-0x = 87). An open contact into the multi-

function input will enable the Thermostat Fault. After an initiation of a Thermostat Fault to disable the Thermostat Fault requires a closed

digital input contact, the drive run command to be open and reset the Thermostat Fault via the drive’s reset button or fault reset input.

Note: An OPE12 fault will occur if H1-xx = 83 and 87. H1-xx cannot be programmed to “83” and “87” at the same time.

Figure 1.50

Figure 50 Thermostat Fault on Operator

Figure 1.51

Figure 51 Wiring Diagram

-DRIVE-

Thermostat

THMS

U2-04 =
U2-05 =

0.00 Hz
0.00 A

H1-04 = 87
(Thermostat FltNC)