Figure 5, For th, B1-02 run source – Yaskawa iQpump Programming Manual User Manual

Page 12: Start/stop from keypad (parameter b1-02 = 0)

Advertising
background image

12

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Figure 1.5

Figure 5 Connection Diagram of PC or PLC

If you want the iQpump drive to receive the “Auto Setpoint” for a network communication option card: Set b1-01= “3: Option

PCB,” and plug a network option board (p/n SI-J) into the 2CN port on the iQpump drive Control PCB. Consult the manual supplied with

the option board for instructions on integrating the iQpump drive into the network system.

The iQpump drive can support the following network communication options. Refer to the appropriate Installation Guide (IG) and

Technical Manual (TM) for further details. These network communications documents can be located at

http://iQpump.yaskawa.com

.

Important: If b1-01 = “3: Option PCB” but a network card is not installed in 2CN, an OPE05 Operator Programming Error will be

displayed on the digital operator and the iQpump drive will not run.

b1-02 Run Source

Start/Stop from Keypad (Parameter b1-02 = 0)

The iQpump drive comes factory programmed for Start and Stop from the Keypad.

The iQpump drive can be programmed to receiver a Run command from four different inputs: digital operator, terminals, serial

communications, or an option PCB.

If the Run command input is determined by the digital operator: Set b1-02 = “0: Operator,” and the hand key will be used to provide

the Run command to the iQpump drive.

If the Run command input is determined by the external terminals: Set b1-02 = “1: Terminals” and initiate an external Run

command by a contact closure between terminals S1 and SN. Refer to

Figure 6

for the connection diagram of the external Run command.

Note: To use the external terminals requires the iQpump drive to be set to “Auto” mode by pressing the Auto key.

• Profibus DP Option Card CM061

Manual: IG.AFD.12

• DeviceNet Option Card CM05X

Manual: IG.AFD.14

• Modbus Plus Option Card CM071

Manual: IG.AFD.17

• Modbus TCP/IP Option Card CM090

Manual: IG.AFD.25

• EtherNet/IP Option Card CM092

Manual: IG.AFD.26

Setting

Description

0

Operator (factory default)

1

Terminals

2

Serial Com

3

Option PCB

Advertising