P3-08 multi pump setpoint decrease – Yaskawa iQpump Programming Manual User Manual

Page 152

Advertising
background image

152

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

Figure 1.115

Figure 120

P3-08 Multi Pump Setpoint Decrease

Setting Range:

0.0 to 6000.0

Factory Default: 0.0

The iQpump drive can be configured for multiplex pumping operation. The multiplex pumping operation can have the system setpoint

decreased each time a pump is staged (turned ON) by programming the amount to be decreased into the Multi Pump Setpoint Decrease

(P3-08). The system’s setpoint will be raised by this amount when each pump is de-staged (turned OFF). Refer to

Figure 121

below.

The units for this parameter are determined by the System Units (P1-02).

Example: Constant Pressure System

System Setpoint: 80 PSI

Pressure Transducer: 150 PSI

Multi Pump Setpoint Increase: 4 PSI

Pump 1 (Running) Setpoint = 80 PSI

Pump 1 + Pump 2 (Running) Setpoint = 76 PSI (80 PSI - 4 PSI)

Pump 1 + Pump 2 + Pump 3 (Running) Setpoint = 72 PSI (80 PSI - 4 PSI - 4 PSI)

Time

SET-POINT

Set-Point + 2 x P3-07

Set-Point + P3-07

PUMP 1

PUMP 1 + 2

PUMP 1 + 2 + 3

PUMP 1 + 2

Set-Point + P3-07

PUMP 1