Yaskawa iQpump Programming Manual User Manual

Page 176

Advertising
background image

176

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

b5-07



01ABH

PI Offset Adjustment
PI Offset

Sets the amount of offset of the output of the PI controller. Set as a% of
fmax.
The PI Offset Adjustment parameter has two different uses. Parameter
b5-07 serves different functions depending on whether it is used on a
standard PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to the output of the PI
function in a non-Differential PI loop. Every time the PI output is
updated, the offset is summed with the PI output. This can be used to
artificially kick-start a slow starting PI loop.
2: If the Drive is configured for Differential PI Regulation (H3-09=16),
then the PI Offset is the targeted maintained differential between the
signal measured on analog input A1 and the signal measured on analog
input A2.

–100.0 to

+100.0

0.0%

Programming

26

b5-08



01ACH

PI Primary Delay Time
Constant
PI Delay Tim

e

Sets the amount of time for a filter on the output of the PI controller.

0.00 to

10.00

0.00 sec Programming

26

b5-09

01ADH

PI Output Level
Selection
Output Level Sel

Determines whether the PI controller will be direct or reverse acting.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)

0 or 1

0

Programming

27

b5-10

01AEH

PI Output Gain Setting
Output Gain

Sets the output gain of the PI controller.

0.0 to 25.0

1.0

Programming

27

b5-12

01B0H

PI Feedback Reference
Missing Detection
Selection
PFb los Det Sel

0: Disabled
1: Alarm
2: Fault

0 to 2

0

Pump Quick

Setup

b5-13

01B1H

PI Feedback Loss
Detection Level
Fb los Det Lvl

Sets the PI feedback loss detection level as a percentage of maximum
frequency (E1-04).

0 to 100

0%

Pump Quick

Setup

27

b5-14

01B2H

PI Feedback Loss
Detection Time
Fb los Det Time

Sets the PI feedback loss detection delay time in terms of seconds.

0.0 to 25.5

1.0 sec

Pump Quick

Setup

27

b5-17

01B5H

PI Accel/Decel Time
Acc/Dec Time

Applies an accel/decel time to the PI setpoint reference.

0.0 to 25.5

0.0 sec

Programming

28

 Denotes that parameter can be changed when the drive is running.

Energy Saving

b8-01

01CCH

Energy Saving Control
Selection
Energy Save Sel

Energy Savings function enable/disable selection
0: Disabled
1: Enabled

0 or 1

0

Programming

29

b8-04

01CFH

Energy Saving
Coefficient Value
Energy Save COEF

Used to fine-tune the energy savings function.

0.0 to

655.00

kVA

Dependent

Programming

29

b8-05

01D0H

Power Detection Filter
Time
kW Filter Time

0 to 2000

20 ms

Programming

29

b8-06

01D1H

Search Operation Voltage
Limit
Search V Limit

0 to 100

0%

Programming

29

Accel / Decel

C1-01



0200H

Acceleration Time 1
Accel Time 1

Sets the time to accelerate from zero to maximum frequency.

0.0 to

6000.0

25.0 sec

Pump Quick

Setup

30

C1-02



0201H

Deceleration Time 1
Decel Time 1

Sets the time to decelerate from maximum frequency to zero.

25.0 sec

Pump Quick

Setup

30

C1-03



0202H

Acceleration Time 2
Accel Time 2

Sets the time to accelerate from zero to maximum frequency when
selected via a multi-function input.

10.0 sec Programming

30

C1-04



0203H

Deceleration Time 2
Decel Time 2

Sets the time to decelerate from maximum frequency to zero when
selected via a multi-function input.

10.0 sec Programming

30

C1-05



0204H

Acceleration Time 3
Accel Time 3

Sets the time to accelerate from zero to maximum frequency when
activated by P3-12. Used for system response stabilization.

50.0 sec Programming

30

C1-06



0205H

Deceleration Time 3
Decel Time 3

Sets the time to decelerate from maximum frequency to zero when
activated by P3-12. Used for system response stabilization.

50.0 sec Programming

30

C1-09

0208H

Fast Stop Time
Fast Stop Time

Sets the time to decelerate from maximum frequency to zero for the
“Fast Stop” function.

0.0 to

6000.0

10.0 sec Programming

30

 Denotes that parameter can be changed when the drive is running.

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.