YASKAWA TM.iQp.02 iQpump Drive Programming Manual

135

The iQpump drive can be configured to allow a maximum number of cycles before initiating a “Pump Over Cycle Fault (POC).” The

drive will determine the maximum number of cycles based on the programmed number in the Sleep Mode: Cycling Protection (P2-06).

One cycle is defined by the drive transferring from normal operation to sleep mode when operating in the Auto Mode. A value of 0

programmed into the Sleep Mode: Cycling Protection (P2-06) will disable this function.

The maximum time allowed between cycles can be programmed in the Sleep Mode: Maximum Cycling Protection Time (P2-07).

The Sleep Mode: Cycling Protection (P2-06) works in conjunction with the Sleep Mode: Maximum Cycling Protection Time (P2-07).

P2-07 Sleep Mode: Maximum Cycling Protection Time

Setting Range:

0 to 3600 sec

Factory Default: 300 sec

The iQpump drive can be configured to allow a maximum number of cycles before initiating a “Pump Over Cycle Fault (POC).” The

number of cycles allowed is determined by programming the Sleep Mode: Cycling Protection (P2-06). The maximum time allowed

between cycles can be programmed in the Sleep Mode: Maximum Cycling Protection Time (P2-07). If no cycling occurs within the

programmed time, the drive will reset the internal cycle register.

The Sleep Mode: Maximum Cycling Protection Time (P2-07) works in conjunction with the Sleep Mode: Cycling Protection (P2-06).

P2-08 Over-Cycling Mode

If P2-08 = “0: Disabled,” the over-cycling mode is disabled.

If P2-08 = “1: Alarm,” then a “Pump Cycling” alarm will occur to indicate a pump over-cycle condition when the maximum number of

cycles has been reached as defined by the Sleep Mode: Cycling Protection (P2-06).

If P2-08 = “2: Pump Over Cycle Fault (POC),” then a “Pump Over Cycle (POC)” fault will occur to indicate a pump over-cycle fault

condition, when the maximum number of cycles has been reached, as defined by the Sleep Mode: Cycling Protection (P2-06).

If P2-08 = “3: Auto Compensation,” then the drive will automatically increase (compensate) the system setpoint by the value

programmed in the Setpoint Compensation (P2-09) parameter.

The compensation will increase each time the maximum number of cycles is reached as defined by the Sleep Mode: Cycling Protection

(P2-06) function. When the setpoint is increased (incremented), the internal over-cycle counter will be reset.

The original setpoint will be restored (decreased) in steps defined by Setpoint Compensation (P2-09) when the pump system has been

operating without cycling for the time programmed in the Maximum Cycle Protection Time (P2-07) parameter.

Over-cycle protection is only active during operation in the Auto Mode and in combination with no-flow sleep functions P2-05 and P2-

07.

Note: Maximum setpoint compensation can be programmed in Maximum Setpoint Compensation (P2-10).

Manually starting and stopping the drive will reset the internal over-cycle counter. Transitioning from Hand to Auto Mode will also reset

the internal over-cycle counter.

Setting

Description

0

Disabled (

factory default)

1

Alarm

2

Pump Over Cycle Fault (POC)

3

Auto Compensation