Yaskawa iQpump Programming Manual User Manual

Page 76

Advertising
background image

76

YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

H3-10 Terminal A2 Gain Setting

Setting Range:

0.0 to 1000.0%

Factory Default: 100.0%

H3-11 Terminal A2 Bias Setting

Setting Range:

-100.0% to +100.0%

Factory Default: 0.0%

Parameters H3-10 and H3-11 perform the same function for the A2 analog input that parameters H3-02 and H3-03 perform for the A1

analog input. Please refer to the parameter description for H3-02 and H3-03 for information about H3-10 and H3-11.

These parameters could be used for final calibration of a factory or field installed pressure to electric transducer input connected to

terminal A2 and AC. This field calibration may be needed if there is a job site variation from the typical 3 to 15 PSIG pneumatic signal

input range.

H3-12 Analog Input Filter Time Constant

Setting Range:

0.00 to 2.00 sec

Factory Default: 0.30 sec

An analog input filter can be used to prevent erratic iQpump drive control when a “noisy” analog reference is used. Parameter H3-12 sets

the time constant for a first order filter that will be applied to both the A1 and A2 analog inputs. The iQpump drive operation becomes

more stable the longer the time programmed, but it becomes less responsive to rapidly changing analog signals.

Figure 1.72

Figure 72 Analog Input Filter Time Constant Effect on “Noisy” Signal

H3-13 Master Frequency Reference Terminal Selection

Parameter H3-13 allows the programmer to select which analog input will serve as the Speed Command input when “Terminals” are

selected as the Auto Mode Speed source (b1-01 = “1: Terminals”), or Terminal is selected as the reference source for the Hand mode (b1-

12 = “1: Terminals”). For the A2 analog input to be an effective selection for the H3-13 parameter, parameter H3-09 must be configured

as Aux Reference (H3-09 = “2: Aux Reference”).

If H3-09

≠2, then the A1 analog input will be used regardless of the setting of parameter b1-12.

Setting

Description

0

Main Fref = A1 (factory default)

1

Main Fref = A2

Analog

Input
Filter

Noisy

input

signal

Analog

input post

Internal Analog Input Valve

(Filtered)