TM.iQp.02 iQpump Drive Programming Manual

Factory Default Settings

The following tables detail the factory default settings for the parameters that are affected by the setting of parameter o2-04.

Table 35 208/240 VAC Drives

Drive Model

CIMR-P7U-
…

-107

Nominal

Hp

Factory

Default

for

b8-04

Factory

Default

for

C6-02

<0032>

Factory

Default

for

E2-01

Factory

Default

for

E2-03

Factory

Default

for

E2-05

Factory

Default

for

L2-02

Factory

Default

for

L2-03

Factory

Default

for

L2-04

Factory

Default

for

L8-02

Factory

Default

for

L8-06

20P4

0.5/0.75

288.2

10 kHz

1.9

1.2

9.842

0.1

0.1

0.3

95× C

5

20P7

2

223.7

10 kHz

3.3

1.8

5.156

0.1

0.2

0.3

95× C

7.5

21P5

1.5/2

169.4

10 kHz

6.2

2.8

1.997

0.2

0.3

0.3

95× C

10

22P2

3

156.8

8 kHz

8.5

3.0

1.601

0.3

0.4

0.3

100 × C

12

23P7

5

122.9

10 kHz

14.0

4.5

0.771

0.5

0.5

0.3

95× C

12

25P5

7.5

94.75

15 kHz

19.6

5.1

0.399

1.0

0.6

0.3

95× C

10

27P5

10

72.69

15 kHz

26.6

8.0

0.288

1.0

0.7

0.3

95× C

17

2011

15

70.44

8 kHz

39.7

11.2

0.230

1.0

0.8

0.3

95× C

21

2015

20

63.13

10 kHz

53.0

15.2

0.138

2.0

0.9

0.3

90× C

17

2018

25

57.87

10 kHz

65.8

15.7

0.101

2.0

1.0

0.6

100× C

15

2022

30

51.79

10 kHz

77.2

18.5

0.079

2.0

1.0

0.6

90× C

24

2030

40

46.27

10 kHz

105.0

21.9

0.064

2.0

1.1

0.6

90× C

20

2037

50

38.16

5 kHz

131.0

38.2

0.039

2.0

1.1

0.6

95× C

18

2045

60

35.78

5 kHz

160.0

44.0

0.030

2.0

1.2

0.6

100× C

20

2055

75

31.35

8 kHz

190.0

45.6

0.022

2.0

1.2

0.1

105× C

17

2075

75/100

23.10

2 kHz

260.0

72.0

0.023

2.0

1.3

0.1

110× C

16

2090

125

20.65

2 kHz

260.0

72.0

0.023

2.0

1.5

0.1

100× C

18

2110

150

18.12

2 kHz

260.0

72.0

0.023

2.0

1.7

0.1

95× C

20

Note:

b8-04 = Energy Savings Coefficient

C6-02 = Carrier Frequency
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level