L4 Speed Command Loss Detection

L4-01 Speed Agreement Detection Level

Setting Range:

0.0 to 200.0 Hz

Factory Default: 0.0 Hz

L4-02 Speed Agreement Detection Width

Setting Range:

0.0 to 20.0 Hz

Factory Default: 2.0 Hz

Parameters L4-01 and L4-02 are user specified levels for use with the Fref/Fout Agree 1, Fref/Set Agree 1, and Freq Detect 1 & 2 digital

output functions. Please refer to the H2 Digital Output Parameters for more information.

L4-05 Frequency Reference Loss Detection Selection

Note: Only available in Hand Mode (P5-01 = 0).

L4-06 Frequency Reference at Loss of Frequency Reference

Setting Range:

0.0 to 100% of previous speed command

Factory Default: 80% of previous speed command

The Drive can be configured to compensate for the loss of its external speed command. An external speed command is considered lost if

it drops 90% of its value in 400 mS or less.

Figure 1.89

Figure 94 Loss of Frequency Reference Timing Diagram

To enable Frequency loss detection, set L4-05 = “1: Enabled @% of PrevRef”. If Frequency Reference Loss Detection is enabled and the

reference is lost, the Drive continues to operate at the speed commanded by parameter L4-06. When the speed command returns, the

Drive again follows the speed command.

Setting H2-01 / H2-02 = “C: Loss of Ref”, configures a digital output as a Frequency Reference Loss indication only when L4-05 = “1”

Enabled @% of PrevRef”.

Note: Only available in Hand Mode (P5-01 = 0).

Setting

Description

0

Disabled

1

Enabled @% of PrevRef (

factory default)

T

Frequency
Reference

Output
Frequency

100%

10%

T = 400 mS

L4 - 06

Time