YASKAWA TM.iQp.02 iQpump Drive Programming Manual

13

Figure 1.6

Figure 6 Connection Diagram of External Start/Stop Switch

If the Run command is determined by Serial Communications: b1-02 = “2: Serial Communications,” and initiate the Run command

through the serial communications. Refer to

Figure 6

(in the previous b1 sequence section) for the connection diagram for serial

communications through the RS232/485 terminals. The following is a simple setup procedure for programming the iQpump drive and PC

Serial communications to initiate Run and Stop commands through serial communications.

1. Program b1-02 = “2: Serial communications”.
2. Program the following H5 parameters:

H5-01 Serial Communication Address: 31

H5-02 Serial Baud Rate: 9600 Baud (setting 3).
H5-03: Serial Communication Parity Selection: None (setting 0)

3. Initiate a Start/Stop command

iQpump command register number: 0001

Stop Command: Transmit value of 0000 (16 bit) to iQpump command address.

Start Command: Transmit value of 0001 (16 bit) to iQpump command address.
Reset Command: Transmit value of 0008 (16 bit) to iQpump command address.

If the Run command input is determined by a network communications option PCB: b1-02 = “3: Option PCB,” and initiate the Run

command through the available network communications option PCB listed below. The Installation Guides (IG) and Technical Manuals

(TM) are available at

http://iQpump.yaskawa.com

.

The iQpump Controller allows for monitoring, diagnostics and control using any of the following communication option cards:

Note: Refer to the communication card instruction manual or consult factory for installation and operation instructions.

Start/Stop from Comm. Option Card (Parameter b1-01 = 3):

The iQpump Controller allows for the setpoint reference to be set via any of the following communication option cards:

• Profibus DP Option Card CM061

Manual: IG.AFD.12

• DeviceNet Option Card CM05X

Manual: IG.AFD.14

• Modbus Plus Option Card CM071

Manual: IG.AFD.17

• Modbus TCP/IP Option Card CM090

Manual: IG.AFD.25

• EtherNet/IP Option Card CM092

Manual: IG.AFD.26

• Profibus DP Option Card CM061

Manual: IG.AFD.12

• DeviceNet Option Card CM05X

Manual: IG.AFD.14

b1

-02 = 1

b

b1-02 = 1