YASKAWA TM.iQp.02 iQpump Drive Programming Manual

45

E2 Motor Setup

E2-01 Motor Rated Current

Setting Range:

10% to 200%

Factory Default: Model Dependent

The Motor Rated Current parameter (E2-01) is necessary information for the iQpump drive motor protection function. The motor

overload protection parameter L1-01 is enabled by default. In addition, motor rated current is used by the torque compensation function

to insure optimum torque production. Set E2-01 to the full load amps (FLA) value stamped on the motor’s nameplate. During Auto-

tuning, it is required for the operator to enter the motor rated current in parameter T1-04 on the Auto-Tuning menu. If the Auto-tuning

operation completes successfully, the value entered into T1-04 will be also written into E2-01.

For applications employing an iQpump drive that is oversized for the motor, E2-01 may be set as low as 10% of the iQpump drive output

current rating. The AMP value in E2-01, however, must always be greater than the “No Load Current” value in parameter E2-03 or an

OPE02 error will be displayed.

E2-03 No Load Current

Setting Range:

Model Dependent (see

Appendix B

)

Factory Default: Model Dependent

Set E2-03 to the motor no-load current at rated voltage and rated frequency. Consult the motor manufacturer for the proper value if the no

load current is not stated on the motor nameplate.

E2-04 Number of Motor Poles

Setting Range:

2 to 48 poles

Factory Default: 2 pole

This parameter sets the number of motor poles used for no-flow detection function and for the calculation of RPM-related parameters.

E2-05 Motor Line-to-Line Resistance

Setting Range:

0.000 to 65.000

Ω

Factory Default: Model Dependent

Sets the line-to-line resistance of the motor’s stator winding. Usually determined by performing Auto-tuning. If Auto-tuning cannot be

completed without error, then manually set E2-05 to the value as determined by the motor manufacturer. Remember this value must be

entered as line-line and not line neutral.

Phase-to-phase Resistance at

Insulation Class Temperature

273 + (25 + insulation class temperature) /2

273 + insulation class temperature

E2-05 =

)

(

X

Where: Insulation class temperature is in

°C