YASKAWA TM.iQp.02 iQpump Drive Programming Manual

83

Related Parameters

The following parameters need to be set correctly to insure proper operation of the iQpump drive when using Modbus communication.

Table 20 Serial Communication Related Parameters

Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02:

1. Monitoring operation status of the Drive
2. Setting and reading iQpump drive parameters
3. Resetting faults
4. Input multi-function commands

Important: An OR operation is performed between the multi-function command input from the PLC and the command input from multi-

function digital input terminals S3 to S7.

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

Number

b1-01

0108H

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

0

Pump Quick

Setup

174

b1-02

0181H

Run Command
Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

1

Pump Quick

Setup

174

H5-01

0425H

Drive Node Address
Serial Com Adr

Selects Drive station node number (address) for terminals R+, R-, S+,
S-.*
Note: An address of “0” disables serial com.

0 to 20

(H5-08=0)

0 to FF

(H5-08=1)

0 to 63

(H5-08=2)

1F

Programming

185

H5-02

0426H

Communication
Speed Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud

0 to 4

3

Programming

185

H5-03

0427H

Communication
Parity Selection
Serial Com Sel

Selects the communication parity for terminals R+, R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

Programming

185

H5-04

0428H

Stopping Method
after Communication
Error
Serial Fault Sel

Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

185

H5-05

0429H

Communication
Error Detection
Selection
Serial Flt Dtct

Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.

0 or 1

1

Programming

185

H5-06

042AH

Drive Transmit Wait
Time
Transmit WaitTIM

Sets the time from when the Drive receives data to when the Drive
sends data.

5 to 65

5 ms

Programming

185

H5-07

042BH

RTS Control
Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 or 1

1

Programming

185

H5-09

0435H

Communication
Error Detection Time
CE Detect Time

Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and H5-
04.

0 to 10.0

(H5-08=0)

0 to 10.0

(H5-08=1)

0 to 90.0

(H5-08=2)

2.0 sec

Programming

186

*Set H5-01 to 0 to disable Drive responses to Modbus communications.