YASKAWA

TM.iQp.02 iQpump Drive Programming Manual

E1-06 Base Frequency

Setting Range:

0.0 to 120.0 Hz

Factory Default: 60.0 Hz

E1-07 Mid Output Frequency A

Setting Range:

0.0 to 120.0 Hz

Factory Default: 3.0 Hz

E1-08 Mid Output Voltage A

Setting Ranges: 0.0 to 255.0 V (240 V Models)

0.0 to 510.0 V (480 V Models)

Factory Defaults: 17.2 V (240 V Models)

34.5 V (480 V Models)

E1-09 Minimum Output Frequency

Setting Range:

0.0 to 120.0 Hz

Factory Default: 1.5 Hz

E1-10 Mid Output Voltage

Setting Ranges: 0.0 to 255.0 V (240 V Models)

0.0 to 510.0 V (480 V Models)

Factory Defaults: 10.3 V (240 V Models)

20.7 V (480 V Models)

E1-11 Mid Output Frequency B

Setting Range:

0.0 to 120.0 Hz

Factory Default: 0.0 Hz

E1-12 Mid Output Voltage B

Setting Ranges: 0.0 to 255.0 V (240 V Models)

0.0 to 510.0 V (480 V Models)

Factory Defaults: 0.0 V (240 V Models)

0.0 V (480 V Models)

Top set up custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the

following condition is true:

E1-09

≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04

E1-13 Base Voltage

Setting Ranges: 0.0 to 255.0 V (240 V Models)

0.0 to 510.0 V (480 V Models)

Factory Defaults: 0.0 V (240 V Models)

0.0 V (480 V Models)

To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be sure that the

following condition is true:

E1-09

≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04