Yaskawa iQpump Programming Manual User Manual

Page 131

Advertising
background image

YASKAWA TM.iQp.02 iQpump Drive Programming Manual

131

Figure 1.100

Figure 105 Sleep Function Based on Output Current

If P2-01 = “2: Feedback”

The iQpump drive can be configured to enter a “sleep” condition based on the feedback signal. The drive will enter the sleep mode when

the feedback signal rises above the programmed Sleep Level (P2-02) for a time specified by the Sleep Delay Time (P2-03).

This function is only active during operation in the Auto Mode.

The Sleep Level Type works in conjunction with the Sleep Level (P2-02), Sleep Delay Time (P2-03), and Alternative Sleep Activate

Level (P2-20).

Note: The feedback signal depends on the PID direction (b5-09). If the PID operation is programmed Reverse Output

direction, the sleep mode will activate when the feedback signal falls below the programmed Sleep Level (P2-02). The

PID will automatically be reset while sleep mode is active.

Start Level Delay

P1-05

Start Level Delay

P1-05

Sleep Delay Time

P2-03

Output Frequency

Sleep Level

P2-02

Min. Frequency

P1-06

STOP, 0Hz

Feedback

System

Set-Point

Start Level

P1-04

0%

Auto Mode Run

OFF Mode

Sleep Active

Wait for Start

Start System

AUTO MODE RUN

AUTO MODE RUN

AUTO MODE RUN

SLEEP ACTIVE

Start System, Incoming Run Command

TIME

START
DELAY

START DELAY

Output Current

Advertising