Function: Fref/Set Agree 1 (Setting: 3)

The “Fref/Set Agree 1” output will close whenever the actual output frequency and the Speed Command are within the Speed Agree

Width (L4-02) of the programmed Speed Agree Level (L4-01).

Figure 1.52

Figure 52 Fref/Set Agree 1 Timing Diagram

Function: Freq Detect 1 (Setting: 4)

A “Freq Detect 1” output will be closed whenever the output frequency is equal to or below the value of the programmed Speed Agree

Level (L4-01). The Speed Agree Width (L4-02) is the hysteresis to the Freq Detect 1 function. Whenever the output frequency

approaches the Speed Agree Level while accelerating it will need to be equal to or exceed the Speed Agree Level (L4-01) plus the Speed

Agree Width (L4-02) before the Freq Detect 1 output will energize.

As the output frequency approaches the Speed Agree Level while decelerating, the Freq Detect 1 output will de-energize exactly at the

Speed Agree Level.

The Freq Detect 1 function is effective during both forward and reverse operation.

Figure 1.53

Figure 53 Freq Detect 1 Timing Diagram

Frequency Agree

Signal

Output Frequency

t

a

Frequency

Reference

a

D t ti

Width (L4 02) X 2

Speed Agree Level

(L4-01)

t

t

Speed Command

Frequency/Set Agree 1

Signal

a - Speed Agree Width (L4-02) X2

ON (CLOSED)

OFF (OPEN)

TIME

Frequency

Detection Signal

Output

Frequency

t

a

a

- Detection Width (L4-02)

L4-01

Detection 1 Signal

ON (CLOSED)

OFF (OPEN)

a - Speed Agree Width (L4-02)

a

t

TIME