YASKAWA TM.iQp.02 iQpump Drive Programming Manual

67

Function: Reset Cmd Active (Setting: 11)

A Reset Cmd Active digital output will close to signal that a Fault reset is being attempted from terminals or Serial Com.

Function: Timer Output (Setting: 12)

This Timer function, that is built into the Drive, is independent of the rest of the iQpump drive operation, i.e. there is no requirement for

a Run command for the timer to operate. A Timer digital output will close b4-01 seconds after a digital input configured as Timer Input

(H1-0x = 18) closes and remains closed. The Timer digital output will remain closed for b4-02 seconds after the Timer digital input opens

and remains open.

Refer to the descriptions of parameters b4-01 and b4-02 for a timing chart of the Timer function.

Function: Trq Det 1 N.C. (Setting: 17)

The Trq Det 1 function ties a digital output to the overtorque/undertorque sensing capabilities of the Drive. If a digital output is

configured as Trq Det 1 N.C., whenever the output current exceeds the level of L6-02 for at least the length of time set in L6-03, the

digital output will open.

The torque detection function has a built-in hysteresis of 10% of the iQpump drive rated output current.

Figure 1.57

Figure 57 Trq Det 1 N.C. Timing Diagram

Function: Reverse Dir (Setting: 1A)

The Reverse Dir digital output will close whenever the iQpump drive is turning the motor in the direction that corresponds to the reverse

direction (CW or CCW). The Reverse Dir digital output will remain closed during deceleration when the rotation is in the reverse

direction.

Figure 1.58

Figure 58 Reverse Direction Timing Diagram

Function: Restart Enabled (Setting: 1E)

Depending on the setting of parameter L5-01, the iQpump drive may be configured to automatically attempt to restart itself after certain

faults. The Restart Enabled output will be closed once the restarts begin and will remain closed until a successful restart is accomplished

or the number of Auto Restart attempts as specified by L5-01 is reached.

A timing diagram for the Auto Restart function is contained in the parameter L5-01 description.

Undertorque Detection

Signal

t

L6-03

L6-02

t

Output Current

b

ON (Closed)

OFF (Open)

L6-01 = 5,6,7, or 8
L6-02 = TD Level 1
L6-03 = TD Delay Time 1
b = 10% of Drive rated current

TIME

Output Frequency

Fwd RUN

Rev RUN

Reverse Dir Output

ON (Closed)

ON (Closed)

ON (Closed)
OFF (Open)

OFF (Open)

t

OFF (Open)

Reverse Dir Output

TIME