TM.iQp.02 iQpump Drive Programming Manual

177

C1-11

020AH

Accel/Decel Switch
Frequency
Acc/Dec SW Freq

Sets the frequency for automatic switching of accel / decel times.
Fout < C1-11: Accel/Decel Time 2
Fout >= C1-11: Accel/Decel Time 1
Multi-function input “Multi-Acc/Dec 1" has priority over C1-11.

0.0 to
200.0

0.0 Hz

Programming

30

S-Curve Acc/Dec

C2-01

020BH

S-Curve Characteristic at
Accel Start
SCrv Acc @ Star

t

0.00 to

2.50

0.20 sec Programming

32

C2-02

020CH

S-Curve Characteristic at
Accel End
SCrv Acc @ End

0.00 to

2.50

0.20 sec Programming

32

Torque Comp

C4-01



0215H

Torque Compensation
Gain
Torq Comp Gain

This parameter helps to produce better starting torque. It determines
the amount of torque or voltage boost based upon motor current and
motor resistance.

0.00 to

2.50

1.00

Programming

33

C4-02

0216H

Torque Compensation
Primary Delay Time
Torq Comp Time

This parameter adjusts a filter on the output of the torque compensation
function. Increase to add torque stability, decrease to improve torque
response.

0 to 10000

200 ms Programming

33

 Denotes that parameter can be changed when the drive is running.

Carrier Freq

C6-01

0223H

Normal Duty Selection
Normal Duty Sel

1: Normal Duty 1
2: Normal Duty 2

1 or 2

2

Programming

34

C6-02

0224H

Carrier Frequency
Selection
CarrierFreq Sel

Carrier frequency sets the number of pulses per second of the output
voltage waveform.
0: Low Noise (Carrier frequency is randomly moduled for lower
audible noise)
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of C6-03 thru C6-05)

0 to F

kVA

Dependent

Programming

34

C6-03

0225H

Carrier Frequency Upper
Limit
CarrierFreq Max

Maximum carrier frequency allowed when C6-02 = F.

0.4 to 15.0

kHz

kVA

Dependent

Programming

34

C6-04

0226H

Carrier Frequency Lower
Limit
CarrierFreq Min

Minimum carrier frequency allowed when C6-02 = F.

0.4 to 15.0

kHz

kVA

Dependent

Programming

34

C6-05

0227H

Carrier Frequency
Proportional Gain
CarrierFreq Gain

Sets the relationship of output frequency to carrier frequency when C6-
02 = F.

0 to 99

0

Programming

34

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

Time

Run
command

Output frequency

ON

C2-02

C2-01

OFF

S-curve is used to further soften the starting ramp.
The longer the S-curve time, the softer the starting
ramp.