P3-13 Friction Compensation Start Frequency

Setting Range:

0.0 to 120.0 Hz

Factory Default: 0.0 Hz

The iQpump drive can be configured for multiplex pumping operation. The pump system may experience an increase of friction when

additional pumps are staged (turned ON). The level when the additional compensation for friction losses can be programmed into the

Friction Compensation Start Frequency (P3-13). This function will activate when the output frequency rises above the Friction

Compensation Start Frequency (P3-13). The maximum compensation at Maximum Output Frequency (E1-04) is specified by the

Maximum Friction Increase at Maximum Frequency (P3-14).

The Friction Compensation Start Frequency (P3-13) works in conjunction with the Maximum Friction Increase at Maximum Frequency

(P3-14).

Note: This function is only active when the Pump Mode (P1-01) is set to 0.

Figure 1.118

Figure 123

P3-14 Maximum Friction Increase at Maximum Frequency

Setting Range:

0.0 to 6000.0

Factory Default: 0.0

The iQpump drive can be configured for multiplex pumping operation. The pump system may experience an increase of friction when

additional pumps are staged (turned ON). The level when the additional compensation for friction losses can be programmed into the

Maximum Friction Increase at Maximum Frequency (P3-14). This function will activate when the output frequency rises above the

Friction Compensation Start Frequency (P3-13). The maximum compensation at Maximum Output Frequency (E1-04) is specified by the

Maximum Friction Increase at Maximum Frequency (P3-14).

OUTPUT

FREQUENCY

P3-13

Time

SET-POINT

P3-14

FMAX

Friction

Compensation

P3-13