TM.iQp.02 iQpump Drive Programming Manual

189

L8-12

04B8H

Ambient Temperature
Setting
Ambient Temp

When the Drive is installed in an ambient temperature exceeding its
rating, Drive overload (OL2) protection level is reduced.

45 to 60°C

45°C

Programming

111

L8-15

04BBH

OL2 Characteristic
Selection at Low Speeds
OL2 Sel @ L-Spd

This parameter assists in protecting the output transistor junctions from
overheating when output current is high and output frequency is low.
0: Disabled
1: Enabled (L8-18 is active)

0 or 1

1

Programming

111

L8-18

04BEH

Soft CLA Selection
Soft CLA Sel

Enables and disables current limit “A”.
0: Disabled
1: Enabled.

0 or 1

1

Programming

112

L8-19 04BFH

OH Frequency Reference
Reduction Level
Fref During OH

Sets the amount of frequency reference reduction when an Overheat
Pre-alarm (OH) is detected.

0.0 to
100.0

20.0%

Programming

112

Hunting Prev

n1-01

0580H

Hunting Prevention
Selection
Hunt Prev Select

0: Disabled (Hunting prevention function disabled.)
1: Enabled (Hunting prevention function enabled.)
If the motor vibrates while lightly loaded, hunting
prevention may reduce the vibration. There is a loss of responsiveness
if hunting prevention is enabled.

0 or 1

1

Programming

113

n1-02

0581H

Hunting Prevention Gain
Setting
Hunt Prev Gain

Gain setting for the Hunting Prevention Function.
If the motor vibrates while lightly loaded and n1-01=1, increase the
gain by 0.1 until vibration ceases. If the motor stalls while n1-01=1
decrease the gain by 0.1 until the stalling ceases.

0.00 to

2.50

1.00

Programming

113

High Slip

n3-01

0588H

High-Slip Braking
Deceleration Frequency
Width
HSB Decel Width

Sets how aggressively the Drive decreases the output frequency as it
stops the motor. If overvoltage (OV) faults occur during HSB, this
parameter may need to be increased.
Note:

Function Deactivated

1.0 to 20.0

5%

Programming

113

n3-02

0589H

High-Slip Braking
Current Limit
HSB Current Ref

Sets the maximum current to be drawn during a HSB stop. Higher n3-
02 settings will shorten motor stopping times but cause increased
motor current, and therefore increased motor heating.
.Note: Function Deactivated

100.0 to

200.0

150%

Programming

113

n3-03

058AH

High-Slip Braking Dwell
Time at Stop
HSB DwelTim@ Stp

Sets the amount of time the Drive will dwell at E1-09 (Minimum
Frequency). If this time is set too low, the machine inertia can cause the
motor to rotate slightly after the HSB stop is complete and Drive
output is shut off.
.Note: Function Deactivated

0.00 to

10.0

1.0 sec

Programming

113

n3-04

058BH

High-Slip Braking
Overload Time
HSB OL Time

Sets the time required for a HSB Overload Fault to occur when the
Drive output frequency does not change for some reason during a HSB
stop. Normally this does not need to be adjusted.
Note:

Function Deactivated

30.0 to
1200.0

40 sec

Programming

113

Monitor Select

o1-01



0500H

User Monitor Selection
User Monitor Sel

Selects which monitor will be displayed upon power-up when o1-02 =
4.

6 to 94

6

Programming

114

o1-02

0501H

User Monitor Selection
After Power-Up
Power-On Monitor

Selects which monitor will be displayed upon power-up.
1: Auto: Setpoint
2: Output Freq
3: Output Current
4: User Monitor (set by o1-01)

1 to 4

1**

Programming

114

o1-05

0504H

LCD Brightness
Adjustment
LCD Contrast

0 to 5

3

Programming

115

o1-06

0517H

User Monitor Selection
Mode
Monitor Mode Sel

Selects the “U1” monitors displayed on the 4th and 5th lines of the
digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1 monitors.)
1: 3 Mon Selectable (Displays U1 monitors set by o1-07 and o1-08.)

0 or 1

1**

Programming

115

 Denotes that parameter can be changed when the drive is running.

Parameter

No.

Modbus

Address

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.

Set Value

Description

5

LCD display becomes dark

3

Standard setting

1

LCD display becomes light