the voltage bias input range for the voltage regulator. The range on these parameters is 4 mA
to 20 mA.

d.

Min Output Voltage (V) and Max Output Voltage (V) - If the Output Type is Voltage, these
parameters must be configured. Set the minimum and maximum voltage to a range equal to
the voltage bias input range for the voltage regulator. The range on these parameters is

−10V

to +10V.

Figure 54. Settings Explorer, Multigen Management, AVR Output

11.

If controlling the governor with an analog signal, open the Governor Output screen in the Settings
Explorer
, under Multigen Management. These parameters are identical to those of the AVR output,
and should be set in a similar manner.

12.

Set up programmable logic to allow the DGC-2020HD to synchronize the generator and close the
generator breaker. In BESTlogicPlus Programmable Logic, click on the Elements tab and drag the
GENBRK (Generator Breaker) element into the main logic screen. See Figure 55.

DGC-2020HD

Synchronizer