Name

Description

Symbol

Mains Breaker

This element is used to connect the breaker open and close
output signals from the DGC-2020HD to physical output
contacts to open and close the mains breaker and map breaker
status feedback to a contact input. In addition, contact inputs
can be mapped to allow switches to be implemented to manually
initiate breaker open and close requests.
This element is only available when the Mains Breaker
Hardware in configured on the Breaker Hardware screen via the
Breaker Management tree branch.
Inputs
Status: This input allows a contact input to be mapped that will
provide breaker status feedback to the DGC-2020HD. When the
contact input is closed, the breaker is indicated to be closed.
When the contact input is open, the breaker is indicated to be
open.
Open: This input allows a contact input to be mapped that can
be used to initiate a manual breaker open request. When this
input is pulsed closed while the DGC-2020HD is in RUN or
AUTO mode, the breaker will open.
Close: This input allows a contact input to be mapped that can
be used to initiate a manual breaker close request. When this
input is pulsed, the mains is stable, and both breakers are open,
a close request will be initiated.
Outputs
The outputs must be mapped to the contact outputs of the DGC-
2020HD that will be used to drive the breaker.
Open: This output is pulsed true (closes the output contact it is
mapped to) when the DGC-2020HD is providing a signal to the
breaker to open. It will be a pulse if the Breaker Output Contact
Type is set to Pulse on the Breaker Hardware screen under
Breaker Management in the Settings Explorer, and the length is
determined by the Open Pulse Time. It will be a constant output
if the Mains Breaker Hardware Contact Type is set to
continuous. Note the pulse time must be set long enough for the
breaker to actually open before the pulse is removed.
Close: This output is pulsed true (closes the output contact it is
mapped to) when the DGC-2020HD is providing a signal to the
breaker to close. It will be a pulse if the Breaker Output Contact
Type is set to Pulse on the Breaker Hardware screen under
Breaker Management in the Settings Explorer, and the length is
determined by the Open Pulse Time. It will be a constant output
if the Mains Breaker Hardware Contact Type is set to
continuous. Note the pulse time must be set long enough for the
breaker to actually open before the pulse is removed.

Note

When using the DGC-2020HD synchronizer, it is
recommended that local DGC-2020HD relay
outputs be used for breaker closing commands to
minimize the possibility of closures outside of
desired breaker closing angles.
If remote (CEM-2020) outputs are to be used for
breaker close commands, it is recommended that
the anticipatory synchronizer type be used, and the
breaker close wait time be adjusted to account for
possible CEM-2020 output delays (typically 50 ms)
to achieve desired breaker closing angles.

Mains Fail Test

When the Set input is true, the DGC-2020HD will exercise its
mains fail transfer function exactly as it would if the mains were
to fail on a mains fail machine.

This can be used as a test of the

mains fail transfer capability of the unit without having to cause a
true mains failure.