Figure 42, Table 35 – Basler Electric DGC-2020HD User Manual

Page 97

Advertising
background image

9469300990 Rev B

87

Figure 42. Settings Explorer, Breaker Management, Gen Condition Detection

Table 35. Settings for Gen Condition Detection

Locator

Setting

Range

Increment

Unit

3 Phase and 1 Phase Condition Settings

A

Dead Gen Threshold Volts

0 to 4,800

1

volts

B

Dead Gen Threshold Per Unit

based on nominal

n/a

per unit

C

Dead Gen Activation Delay

0.1 to 600

0.1

seconds

D

Gen Failed Activation Delay

0.1 to 600

0.1

seconds

Overvoltage and Undervoltage Settings

E

Pickup (V L-L) Volts

10 to 99,999

1

volts