Cem-2020, Features, Specifications – Basler Electric DGC-2020HD User Manual

Page 335: Operating power, Maximum consumption, Contact inputs, Contact outputs, Ratings, Cem-2020h, Can interface

Advertising
background image

9469300990 Rev B

325

DGC-2020HD

CEM-2020

CEM-2020

The Contact Expansion Module (CEM-2020) is an optional remote device that provides additional DGC-
2020HD contact inputs and outputs. Two types of modules are available. A low current module (CEM-
2020) provides 24 contact outputs and high current module (CEM-2020H) provides 18 contact outputs.
Up to four CEM-2020s may be used with one DGC-2020HD.

Features

CEM-2020s have the following features:

10 Contact Inputs

18 Contact Outputs (CEM-2020H) or 24 Contact Outputs (CEM-2020)

Functionality of Inputs and Outputs assigned by BESTlogic

Plus Programmable Logic

Communications via CAN

Specifications

Operating Power

Nominal .................................................. 12 or 24 Vdc
Range ...................................................... 8 to 32 Vdc (Withstands cranking ride-through down to

6 Vdc for 500 ms)

Maximum Consumption
CEM-2020 ............................................... 14 W
CEM-2020H............................................. 8 W

Contact Inputs

The CEM-2020 contains 10 programmable inputs that accept dry contacts.

Time from a CEM-2020 input application to:

Shut down the generator via an alarm = 700 ms max

Close a relay on board the DGC-2020HD = 300 ms max

Close a relay on board the CEM-2020 = 550 ms max

Contact Outputs

Ratings

CEM-2020

Outputs 1 through 12 .............................. 1 Adc at 30 Vdc, Form C, gold contacts
Outputs 13 through 24 ............................ 4 Adc at 30 Vdc, Form C

CEM-2020H

Outputs 1 through 12 .............................. 2 Adc at 30 Vdc, Form C, gold contacts
Outputs 13 through 18 ............................ 10 Adc at 30 Vdc, Form C

CAN Interface

Differential Bus Voltage ........................... 1.5 to 3 Vdc
Maximum Voltage ...................................

–32 to +32 Vdc with respect to negative battery terminal

Communication Rate ............................... 250 kb/s