Voltage and current sensing, Generator voltage, Bus voltage – Basler Electric DGC-2020HD User Manual

Page 63: Generator and bus current

Advertising
background image

9469300990 Rev B

53

Voltage and Current Sensing

The DGC-2020HD senses generator voltage, generator current, and bus voltage through dedicated,
isolated inputs.

Generator Voltage

The DGC-2020HD accepts either line-to-line or line-to-neutral generator sensing voltage over the range of
12 to 576 volts rms L-L (7 to 333 volts rms L-N). Single-phase generator voltage is sensed across phases
A and B. Generator voltage sensing terminals are listed in Table 22.

Table 22. Generator Voltage Sensing Terminals

Terminal

Description

86 (GEN VA)

A-phase generator voltage sensing input

88 (GEN VB)

B-phase generator voltage sensing input

90 (GEN VC)

C-phase generator voltage sensing input

91 (GEN VN)

Neutral generator voltage sensing input

Bus Voltage

Sensing of bus voltage enables the DGC-2020HD to detect failures of the mains (utility). The DGC-
2020HD accepts bus sensing over the range of 12 to 576 volts rms L-L (7 to 333 volts rms L-N).
Controllers with style number xxx2xxxxx measure bus voltage sensing to perform automatic
synchronization of the generator with the bus. Single-phase bus voltage is sensed across phases A and
B. Bus voltage sensing terminals are listed in Table 23.

Table 23. Bus Voltage Sensing Terminals

Terminal

Description

93 (BUS 1 VA)

Bus 1 A-phase voltage sensing input

95 (BUS 1 VB)

Bus 1 B-phase voltage sensing input

97 (BUS 1 VC)

Bus 1 C-phase voltage sensing input

98 (BUS 1 VN)

Bus 1 Neutral voltage sensing input

100 (BUS 2 VA)

Bus 2 A-phase voltage sensing input

101 (BUS 2 VB)

Bus 2 B-phase voltage sensing input

103 (BUS 2 VC)

Bus 2 C-phase voltage sensing input

104 (BUS 2 VN)

Bus 2 Neutral voltage sensing input

Generator and Bus Current

The DGC-2020HD has sensing inputs for A-phase, B-phase, and C-phase generator current. One, or up
to four (optional), user-programmable CTs are provided for sensing current on bus 1, optional bus 2, and
generator ground current. Depending on the style number, a DGC-2020HD has a nominal sensing current
rating of 1 Aac or 5 Aac. A style number of 1xxxxxxxx indicates 1 Aac nominal current sensing and a style
number of 5xxxxxxxx indicates 5 Aac nominal current sensing. Generator current sensing terminals are
listed in Table 24 and load bus current sensing terminals are listed in Table 25.

DGC-2020HD

Voltage and Current Sensing

Advertising