Specifications, Operating power, Power consumption – Basler Electric DGC-2020HD User Manual

Page 15: Battery ride through, Current sensing, Generator cts, Available programmable cts, 1 aac current sensing, 5 aac current sensing, Voltage sensing

Advertising
background image

9469300990 Rev B

5

Specifications

DGC-2020HD electrical and physical characteristics are listed in the following paragraphs.

Operating Power

Nominal ............................................ 12 or 24 Vdc
Range ............................................... 6 to 32 Vdc
Terminals.......................................... 48 (+), 49 (–), 50 (chassis ground)

Power Consumption

Sleep Mode ...................................... 12.7 W - LCD heater off, all relays de-energized, and analog outputs

disabled

Normal Operational Mode ................ 18.1 W - Run mode, LCD heater off, START and RUN relays

energized, six programmable relays energized, and analog outputs
enabled

Maximum Operational Mode ............ 25 W - Run mode, LCD heater on, all relays energized, and analog

outputs enabled

Battery Ride Through

Starting at 10 Vdc, withstands cranking ride-through down to 0 Vdc for 50 ms

Current Sensing

Burden .............................................. 1 VA

Generator CTs

Terminals.......................................... 1 (+), 2 (–) (A-phase)

3 (+), 4 (–) (B-phase)

5 (+), 6 (–) (C-phase)

Available Programmable CTs

AUX 1Terminals ............................... 7 (+), 8 (–)
AUX 2 Terminals .............................. 9 (+), 10 (–)
AUX 3 Terminals .............................. 11 (+), 12 (–)
AUX 4 Terminals .............................. 13 (+), 14 (–)
(Programmable CTs AUX 2, 3, and 4 are optional with style number xxxxxxxEx.)

1 Aac Current Sensing

Continuous Rating ............................ 0.02 to 1.5 Aac
1 Second Rating ............................... 10 Aac

5 Aac Current Sensing

Continuous Rating ............................ 0.1 to 7.5 Aac
1 Second Rating ............................... 50 Aac

Voltage Sensing

Range ............................................... 12 to 576 V rms, line-to-line
Frequency ........................................ 50/60 Hz
Frequency Range ............................. 10 to 90 Hz
Burden .............................................. 1 VA
1 Second Rating ............................... 720 V rms

DGC-2020HD

Specifications

Advertising