Metering, Generator and bus voltage (rms), Generator current (rms) – Basler Electric DGC-2020HD User Manual

Page 18: Generator and bus frequency, Apparent power

Advertising
background image

8

9469300990 Rev B

Terminals
Output 1............................................ 15, 18 (common)
Output 2............................................ 16, 18 (common)
Output 3............................................ 17, 18 (common)
Output 4............................................ 19, 22 (common)
Output 5............................................ 20, 22 (common)
Output 6............................................ 21, 22 (common)
Output 7............................................ 23, 26 (common)
Output 8............................................ 24, 26 (common)
Output 9............................................ 25, 26 (common)
Output 10.......................................... 27, 30 (common)
Output 11.......................................... 28, 30 (common)
Output 12.......................................... 29, 30 (common)

The programmable relays share common terminals: terminal 18 is used for outputs 1, 2, and 3, terminal
22 is used for outputs 4, 5, and 6, terminal 26 is used for outputs 7, 8, and 9, 30 is used for outputs 10,
11, and 12.

Metering

Generator and Bus Voltage (rms)

Metering Range ................................ 0 to 576 Vac (direct measurement)

577 to 9,999 Vac (through VT using VT ratio setting)

VT Ratio Range ................................ 1:1 to 125:1 in primary increments of 1
Accuracy

* ......................................... ±1.0% of programmed rated voltage or ±2 Vac

Display Resolution ........................... 1 Vac

* Voltage metering indicates 0 V when generator voltage is below 2% of the full-scale rating.

Generator Current (rms)

Generator current is measured at the secondary windings of user-supplied 1 A or 5 A CTs.
Metering Range ................................ 0 to 5,000 Aac
CT Primary Range ........................... 1 to 5,000 Aac in primary increments of 1 Aac
Accuracy

* ......................................... ±1.0% of programmed rated current or ±2 Aac

Display Resolution ........................... 1 Aac

* Current metering indicates 0 A when generator current is below 2% of the full-scale rating.

Generator and Bus Frequency

Frequency is sensed through the generator and bus voltage inputs (phases A and B).
Metering Range ................................ 10 to 90 Hz
Accuracy...........................................

±0.25% or 0.05 Hz

Display Resolution ........................... 0.1 Hz

Apparent Power

Indicates total kVA and individual line kVA (4-wire, line-to-neutral or 3-wire, line-to-line).

Measurement/Calculation Methods

Total ................................................. kVA = (V

L-L

× I

L

×√3) ÷ 1000

4-Wire, Line-to-Neutral ..................... kVA calculated with respect to neutral
3-Wire, Line-to-Line .......................... A-phase kVA = V

AB

× I

A

÷ 1000 ÷ √3

B-phase kVA = V

BC

× I

B

÷ 1000 ÷ √3

C-phase kVA = V

CA

× I

C

÷ 1000 ÷ √3

Accuracy...........................................

±2% of the full-scale indication or ±2 kVA *†

* kVA metering indicates 0 kVA when the generator kVA is below 2% of the full-scale rating.
† Applies when temperature is between

−40°C to +70°C (–40°F to +158°F).

Specifications

DGC-2020HD