Basler Electric DGC-2020HD User Manual

Page 218

Advertising
background image

208

9469300990 Rev B

Name

Description

Symbol

Fuel Leak
Detect

True when the Fuel Leak Detect input is
true, the Alarm Type is set to Status Only,
and the activation delay has expired.

Generator
Breaker Status

True when the generator breaker is closed.

Generator Dead

True when the Gen Dead condition settings
have been exceeded.

Generator Fail

True when the Gen Fail condition settings
have been exceeded.

Generator
Forward
Rotation

True when the generator rotation matches
the Phase Rotation setting.

Generator
Reverse
Rotation Status

True when the generator rotation is
opposite of the Phase Rotation setting.

Generator
Stable

True when the Gen Stable condition
settings have been exceeded.

Generator Test

True when the Exercise Timer has started
the generator.

Generator Test
Loaded

True when the Exercise Timer has started
the generator and Run with Load is
selected.

GOV Output
Out of Range

True when the GOV Output Limit settings
have been exceeded.

Grounded Delta
Override

True when the Grounded Delta Override
input is true.

Idle Request

True when the Idle Request logic element
is true.

Lamp Test

True when the Lamp Test logic element is
true or the Lamp Test button is pressed on
the front panel.

Load Take Over

True when the Load Take Over logic
element is true.

Low Coolant
Level

True when the Low Coolant Level function
is configured as an alarm or pre-alarm and
the activation delay has expired. In
addition, true when CAN bus is enabled
and the Low Coolant Level Alarm or Pre-
Alarm threshold has been exceeded.

Low Line
Override

True when the Low Line Override logic
element is true.

LS Output Out
of Range

True when the LS Output Limit settings
have been exceeded.

Mains Breaker
Status

True when the mains breaker is closed.

BESTlogic

Plus

DGC-2020HD