Remote thermocouple inputs configuration, Input setup, Label text – Basler Electric DGC-2020HD User Manual

Page 327: Hysteresis, Arming delay

Advertising
background image

9469300990 Rev B

317

DGC-2020HD

AEM-2020

Table 88. Settings for AEM x RTD Input #y

Locator

Setting

Range

Increment

Unit

A

Label Text

n/a

n/a

n/a

B

Hysteresis

0 to 100

0.1

%

C

RTD Type

10 Ohm Copper or
100 Ohm Platinum

n/a

n/a

D

Arming Delay

0 to 300

1

seconds

E

Out of Range Alarm Type

Status Only, Pre-

Alarm, or Alarm

n/a

n/a

F

Mode

Disabled, Over, or

Under

n/a

n/a

G

Threshold

–50 to 250

1

degrees C

–58 to 482

1

degrees F

H

Activation Delay

0 to 300

1

seconds

I

Alarm Configuration

Status Only, Pre-

Alarm, or Alarm

n/a

n/a

Remote Thermocouple Inputs Configuration

Two remote thermocouple inputs provide metering of exhaust temperatures. An element can be
configured to trip when the metered input increases above or decreases below the user-defined
threshold.

The two, identical remote thermocouple input protection elements are designated AEM x Thermocouple
Input #1 and AEM x Thermocouple Input #2 (where x = 1 to 4). Element logic connections are made on
the BESTlogic

Plus screen in BESTCOMSPlus® and element operational settings are configured on the

AEM x Thermocouple Input #y (where x = 1 to 4 and y = 1 or 2) settings screen in BESTCOMSPlus.

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Inputs, Remote Thermocouple
Inputs
Front Panel Navigation Path:
Settings Explorer > Programmable Inputs > Remote Thermocouple Inputs

Input Setup

Label Text

In order to make identification of the remote thermocouple inputs easier, each of the inputs can be given
a user-assigned label. The label is an alphanumeric string with a maximum of 16 characters.

Hysteresis

The hysteresis setting provides a level of hysteresis between a threshold detection tripping and dropping
out. For instance, if the hysteresis is set for 5% and the threshold is set as an over threshold, once the
threshold detection trips, the measured value must drop to 95% of the threshold before the threshold
detection will drop out. This hysteresis helps prevent rapid or repeated transitions between trip and
dropout in cases where the measured input is nearly equal to a level equal to the threshold.

If the threshold is set as an under threshold with 5% hysteresis, once the threshold detection trips, the
measured value must rise to 105% of the threshold before the threshold detection will drop out.

Arming Delay

A user-adjustable arming delay disables remote thermocouple input protection during engine startup. If
the arming delay is set to zero (0), the input protection is active at all times, including when the engine is
not running. If the arming delay is set to a non-zero value, the input protection is inactive when the engine

Advertising