Kw load controller tuning procedure – Basler Electric DGC-2020HD User Manual

Page 375

Advertising
background image

9469300990 Rev B

365

Tuning of KD can be achieved through the following steps. First set TD=0 to eliminate filtering. Raise
speed KD and check for stability. Each time KD is raised, manually displace the governor lever or change
the speed trim set point and see that control is regained in a stable manner. Raise KD until the system is
unstable, and then lower it to half the value where instability is first attained.

If high frequency noise seems to be entering the system, set TD to 0.001 and see if the noise induced
behavior is reduced. Raise TD until desired reduction of noise behavior is achieved. Once TD has been
set, tune KD again. TD ranges from 0 to 1 with an increment of 0.001. If noise again appears to be a
problem, adjust TD until desired behavior is achieved, and then retune KD.

kW Load Controller Tuning Procedure

Once desired voltage and speed controller performance is obtained, the kW load controller can be tuned.
Set the Kp, Ki, and Kd gains in kW load controller to 0. Set the Kg value to 0.1.

KP - Proportional Gain

Set an initial value of 1 for KP.

Close the breaker onto a load. Parallel a second generator with the unit being tuned and check for stable
load sharing. Then open the generator breaker on the second generator and check that the unit being
tuned is still stable. Since KI is zero at this point, there may be some small error in the load sharing. The
important thing is that stable load sharing is achieved.

Raise KP and repeat the test until unstable operation occurs. Lower KP to half the value where unstable
operation was first attained.

If it is not possible to obtain stable kW operation, it may be necessary to reduce the control gains in the
governor that has its analog bias input driven by the DGC-2020HD.

KI - Integral Gain

Set the initial value of KI to be a tenth of the value set for KP.

Each time KI is set, parallel a second generator with the unit being tuned, and check for stable load
sharing then open the generator breaker on the second generator and check that the unit being tuned is
still stable. If the system is not stable, lower KI and repeat the test.

Repeat this procedure, raising KI until the system is unstable, and then lower it to half the value where
instability is first attained.

KD - Derivative Gain

If the performance with KP and KI alone is satisfactory, you may stop here. Otherwise, KD, the derivative
controller gain, can be used in conjunction with TD, the noise filter constant, to reduce overshoot obtained
with the PI control. Setting KD and TD is an iterative process. Start with small values of KD such as 0.1 or
half the KI value, whichever is less.

TD is the constant of the low pass filter which filters the controller input if high frequency interference
presents a problem when derivative control is employed. TD ranges from 0 to 1. TD=0 is no filtering,
TD=1 is heaviest filtering.

Tuning of KD can be achieved through the following steps. Raise load control KD and check for stability.
Each time KD is raised, parallel another generator with the unit being tuned, and check for stable load
sharing. Then drop the second generator and check that the unit being tuned is still stable. Raise KD until
the system is unstable, and then lower it to half the value where instability is first attained. If high
frequency noise seems to be entering the system, raise TD and tune KD again. TD ranges from 0 to 1.

If high frequency noise seems to be entering the system, set TD to 0.001 and see if the noise induced
behavior is reduced. Raise TD until desired reduction of noise behavior is achieved. Once TD has been
set, tune KD again. TD ranges from 0 to 1 with an increment of 0.001. If noise again appears to be a
problem, adjust TD until desired behavior is achieved, then retune KD.

DGC-2020HD

Tuning PID Settings

Advertising