background image

9469300990 Rev B

65

Programmable Functions

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Inputs, Programmable Functions
Front Panel Navigation Path:
Settings > Programmable Inputs > Programmable Functions

Any of the 16 contact inputs can be programmed to recognize any one of 10 function types:

Automatic Transfer Switch (ATS) - Start and run the generator while the ATS input is true and the
DGC-2020HD is in Auto mode.

Grounded Delta Override - Uses Grounded Delta sensing if the generator connection is set for
Delta.

Battle Override - The alarms programmed to shut down the unit will be overridden and ignored.

Low-Line Override - The 51, 27, and 59 settings are scaled by the low-line scale factor setting.

Single-Phase Override - The unit switches to single-phase sensing configuration and uses the
Single Phase Override Sensing setting (A-B or A-C).

Single-Phase A-C Override - Indicates to the DGC-2020HD that the machine is configured for
single-phase A-C. This is to be used in conjunction with the single-phase override programmable
function.

Emergency Stop - Opens the Start, Run, and Pre output relays and annunciates an ESTOP
alarm.

Battery Charger Fail - When the selected input is invoked, a user selectable pre-alarm or alarm is
annunciated after the activation delay.

Low Coolant Level - When the selected input is invoked, a Low Coolant Level pre-alarm or alarm
is annunciated after the activation delay.

Fuel Leak Detect - When the selected input is invoked, a Fuel Leak pre-alarm or alarm is
annunciated after the activation delay.

An Alarm Configuration setting of Status Only prevents a function from being triggered by a contact input.
Programmable function status is available in BESTlogic™Plus Programmable Logic when the “None”
alarm configuration setting is selected.

The BESTCOMSPlus Programmable Functions screen is illustrated in Figure 25. Settings are listed in
Table 31.