Governor Output

The governor output of the DGC-2020HD is used to change the speed setpoint of the generator. If the
response is set for increasing, an increased bias will increase the speed. If the response is set for
decreasing, an increased bias will decrease the speed. Settings are provided for minimum output current,
maximum output current, minimum output voltage, and maximum output voltage.

The BESTCOMSPlus Governor Output screen is illustrated in Figure 62. Settings are listed in Table 40.

Figure 62. Settings Explorer, Multigen Management, Governor Output

Table 40. Settings for Governor Output

Locator

Setting

Range

Increment

Unit

A

Parameter Selection

n/a

n/a

B

Output Type

Voltage, Current, or

PWM

n/a

n/a

C

Response

Increasing or

Decreasing

n/a

n/a

D

Out of Range Activation Delay

0 to 300

1

seconds

E

Alarm Configuration

Status Only, Pre-

Alarm, or Alarm

n/a

n/a

F

Param Min

–999,999 to 999,999

0.1

n/a

G

Param Max

–999,999 to 999,999

0.1

n/a

H

Min Output Current

4 to 20

0.1

milliamps

I

Max Output Current

4 to 20

0.1

milliamps

J

Min Output Voltage

–10 to 10

0.1

volts

K

Max Output Voltage

–10 to 10

0.1

volts

L

Min Output PWM

0 to 100

0.1

%

M

Max Output PWM

0 to 100

0.1

%

∗ See Parameter Selection, below.

Multiple Generator Management